32
Emergency stop
signal
External
interrupt signal
Origin proximity
signal
00
Positioning completed
flag
01
Bank completed flag
02
At-origin flag
03
Alarm flag
04
Emergency stop flag
05
Error flag
06
Zone 0 flag
07
Zone 1 flag
08
Zone 2 flag
09
Teaching completed flag
10
Transfer completed flag
11
No-origin flag
12
Busy flag
13
CW limit flag
14
CCW limit flag
15
STOP flag
Word
Bit
n+6
n+7
n+8
n+9
Present
position
(rightmost 4
digits)
n+5
Origin signal
Output code
Positioning
action no.
Error
code
Direction digit
Present position
(leftmost 3 digits)
3–5
IR Area Data Format
Data is allocated either by bit or by word, though it is often input and output
by decimal digit, i.e., four bits (BCD). Position data is held in two adjacent
words, generally with a direction digit, in the following format.
direction
10
3
10
2
10
1
10
0
10
4
10
5
10
6
0
1
CW
CCW
highest word
lowest word
Note that the rightmost word is always the lowest word. If the two words were
n+8 and n+9, for example, the rightmost word would be n+8 and the leftmost
would be n+9. Furthermore, the rightmost digit in each word begins in the
lowest bits. Thus, the digits x10
4
and x10
0
above would be held in bits 00
through 03 of their respective words. The direction digit also provides other
information when required.
Speeds, Acceleration,
and Deceleration
Only one word is used to store speeds, the acceleration, and the decelera-
tion. The formats for these are as follows:
IR Area Data Format
Section 3–5