Error Code List
Appendix B
124
Error
ORIGIN RETURN
disabled
HIGH-SPEED
JOG disabled
LOW-SPEED JOG
disabled
INCH disabled
Emergency stop
executed
CW limit
CCW limit
No origin proximity
signal
Error code
5200
5300
5400
5500
6000
6100
6101
6200
Problem
ORIGIN RETURN cannot be executed
because of data for ORIGIN RETURN
speed or backlash compensation that
generated alarm.
HIGH-SPEED JOG cannot be executed
because of data for HIGH-SPEED JOG
speed, initial speed, acceleration, decel-
eration, or backlash compensation that
generated an alarm.
LOW-SPEED JOG cannot be executed
because of data for LOW-SPEED JOG
speed, initial speed, or backlash compen-
sation that generated an alarm.
INCH cannot be executed because of
data for backlash compensation that gen-
erated an alarm.
Feeding has been stopped by emergency
stop signal input.
Feeding has been stopped by CW limit
signal input.
Feeding has been stopped by CCW limit
signal input.
No proximity signal is detected between
the CCW and CW limits even though pin
#3 on DIP switch designates a proximity
signal.
Correction
Read out alarm code and correct and
correct data accordingly.
Check wiring.Turn off emergency
stop signal and execute RELEASE
PROHIBIT and ORIGIN SEARCH.
Check wiring. Execute RELEASE
PROHIBIT and then feed counter-
clockwise using HIGH-SPEED JOG,
LOW-SPEED JOG, or INCH (or exe-
cute ORIGIN SEARCH, RESET ORI-
GIN or TRANSFER DATA after RE-
LEASE PROHIBIT).
Check wiring. Execute RELEASE
PROHIBIT and then feed clockwise
using HIGH-SPEED JOG,
LOW-SPEED JOG, or INCH (or exe-
cute ORIGIN SEARCH, RESET ORI-
GIN or TRANSFER DATA after RE-
LEASE PROHIBIT).
Check DIP switch setting, wiring of
proximity signal, and signal type
(N.C. or N.O.).
(continued)