Example 2:
Using Dwell Time
In this example, the completion code for positioning action #1 is set at 1
(pause), with the dwell time set at 0.5 s. The completion code for positioning
action #2 is set at 0 (single), with the dwell time set at 1.0 s.
Pulse output
1
0
1
0
1
0
0.5 s
1.0 s
Time
#1
#2
START
(word n, bit 00)
Positioning completed
flag (word n+5, bit 00)
Busy flag
(word n+5, bit 12)
Example 3: Using START
With Single or Bank End
Positioning Actions
Positioning sequences combining several pause and/or continuous position-
ing actions normally are ended by a single or bank end positioning action.
When the last positioning action is completed, including any dwell time desig-
nated for it, the positioning completed flag turns ON and busy flag turns OFF.
START is then required to begin further execution of positioning actions.
START is also required to restart operation after the STOP command has
been executed. (See 4–10 External Interrupt Commands for details and ex-
amples.)
Start