12
2–1
Switch Settings
Always turn off PC power before setting the unit number switch. Use a regu-
lar screwdriver, being careful not to damage the slot in the screw. Be sure not
to leave the switch midway between settings.
Switch
Function
Used to set the unit number (between 0 and 9).
Do not set the same number for more than one Unit.
Doing so will cause an error and prevent operation.
Not used.
Unit number
(”Machine no.”)
Mode
Back Panel DIP Switch
These pins must be set before the Position Control Unit is mounted.
Pin no.
Name
Output pulse
selector
Origin search
direction
Origin proximity
present/absent
Origin proximity
signal type
Origin signal type
External interrupt
selection*
External interrupt
response*
Nondirectional pulse and
direction signal outputs.
CCW
Present
N.O. input
N.O. input
Fixed via pin #7
CHANGE SPEED
Not used.
Separate CW and
CCW pulse outputs
CW
Absent
N.C. input
N.C. input
Determined by
IR bit (word n, bit 06)
STOP
ON
OFF
1
2
3
4
5
6
7
8
*External interrupt processing is determined by pins #6 and #7 in combination with bit 06 of IR word n (n = 100 + 10 x unit
number). Refer to 4–10 External Interrupt Commands for details.
Switch Settings
Section 2–1