28
3–2
Output Pulses
The Position Control Unit can be set to output either independent CW and
CCW pulses or a nondirectional pulse and a direction signal. Set pin #1 on
the back-panel DIP switch to designate the target type of output. (See 2–1
Switch Settings.)
CW and CCW Pulse
Outputs
ON
OFF
CW pulse train
OFF
ON
CCW pulse train
Nondirectional Pulse
and Direction Signal
Outputs
Pulse train
Direction output
ON
OFF
ON
OFF
1 ms min.
CW: ON
CCW: OFF
CW
CCW
3–3
Writing Data
Data is written, via the Programming Console, into the section of the DM
area designated for Special I/O Units. The specific words are DM 1000-1999,
with 100 of these words allocated for each unit number assigned to a Posi-
tion Control Unit. Written data is effective the next time power is turned on or
when the system is restarted with the restart bit in the AR area. To write data,
use the 3-word change operation of the Programming Console.
Key Input Sequence
Programming Console Display
D1824D1823D1822
0012 5000 2000
The above procedure prepares DM 1824 for change, and new data can be
keyed in. Pressing the CHG key again moves the cursor to DM 1823. After
inputting data, press the write key to execute the rewrite. In the above exam-
ple, positioning action #0 of Unit #8 is shown.
Starting
When starting the Position Control Unit, the OUT refresh area is used. (The
OUT refresh area comprises the first five of the ten IR words allocated to
each Unit as refresh area. See 3–4 Data Configuration and Allocation for de-
Writing Data
Section 3–3