M2DC Series Hardware Manual
82
Rev. 1.1
2018/04
400-820-9661
Software Configuration
On the Motor Configuration page - Control Mode Settings select pulse input type and input filter
type.
7.2.3 Control Pulse Dividing Switch
Input X9 is used as the control pulse dividing switch function. When this function is on, it will allow the
drive to change the number to encoder counts per motor revolution. The first pulse dividing ratio is set via
parameter P-39 (EG), the second pulse dividing ratio is set via P-40 (PV). The second digit of P-65 (MI)
(right to left) is used to set switching conditions.
In factory default mode, pulse dividing switch is disabled. It can be set by M Servo Suite or parameter
P-65 (MI) directly from the drive’s control panel.
Signal
Name
PIN
P-65 (MI)
Condition
Function
X9
X9 (26)
□□1□
Closed
Use 1st pulse dividing ratio ------ P-39 (EG)
Open
Use 2nd pulse dividing ratio ------ P-40 (PV)
□□2□
Closed
Use 2nd pulse dividing ratio ------ P-40 (PV)
Open
Use 1st pulse dividing ratio ------ P-39 (EG)
□□3□
(default)
Always use 1st pulse dividing ratio ----P-39 (EG)
NOTE: ONLY set the pulse dividing ratio function, when no pulse command is being sent
into the drive, i.e. the motor is NOT moving.
Software Configuration
On the Drive Configuration page - Input & Output select X9 input to set up.