7.4.3.4 Analog Deadband
In analog control mode, even when the input voltage is 0V, it is impossible to ensure that the input voltage
is absolutely zero due to external interference. In some cases, it might case motor turn slowly in either
direction. Therefore, it is recommended that a reasonable deadband value be set up to prevent this issue.
It can be set by M Servo Suite or P-57 (AD2) directly from the drive’s control panel.
Parameter
Name
Data Range
Default
value
Unit
Description
P-57 (AD2)
Deadband for analog input 2
0 - 255
0
mV
Set deadband for analog input 2
P-58 (AD3)
Differential analog Deadband
0 - 255
0
mV
Set deadband for differential analog input
Setting Via Software
7.4.3.5 Run/Stop and Direction signal
In analog torque mode, external input X1 can set as run/stop switch, X2 can set as direction switch.
Signal
Name
PIN
Condition
Function
Description
X1
X1+ (3)
Closed
Torque mode run/
stop switch
When motor running, analog voltage defines motor
output torque
X1+ (4)
Open
In this mode, even with analog input, motor will not
turn
X2
X2+ (5)
Closed
Torque mode
direction switch
Change current motor rotary direction
X2+ (5)
Open
Function not used
Setting Via Software