M2DC Series Hardware Manual
Bit 6: Checksum Type
Bit 7: Little endian or big endian used in MODBUS type drive
Bit 8: Four wires/two wires for RS-485 communication
P-77 (TD)
Transmit delay
Data Range
Default
Unit
Data type
0 - 100
2
---
DEC
The time delay used by the drive when responding to a command that requests a response. Typically this
is needed when using the 2-wire RS-485 interface (half-duplex). Because the same wires are used to both
receive and transmit a time delay is usually needed to allow transition time.
P-78 (BR)
Baud rate
Data Range
Default
Unit
Data type
1 - 5
1
---
DEC
This parameter sets the bit rate (baud) for serial communications. At power up a drive will send its power-
up packet detected after 1 second and the drive is configured for SCL or Q operation (see PM command)
the drive will set the baud rate according to the value stored in the Baud Rate NV parameter. A Host
system can set the baud rate at anytime using this command.
1:
9600bps
2:
19200bps
3:
38400bps
4:
57600bps
5: 115200bps
P-79 (DA)
RS-485 Address
Data Range
Default
Unit
Data type
1 - 32
32
---
DEC
The individual drive address character for multi-drop RS-485/MODBUS communications. This command
is not required for single-axis (point-to-point) or RS-232 communications.
Modbus Address
SCL Address
Modbus Address
SCL Address
1
1
17
!
2
2
18
“
3
3
19
#
4
4
20
$
5
5
21
%
6
6
22
&
7
7
23
‘
8
8
24
(
9
9
25
)
10
:
26
*
11
;
27
+
12
<
28
,
13
=
29
-
14
>
30
.
15
?
31
/
16
@
32
0