157
3. FUNCTION
3.7 Diagnostics
1
2
3
4
5
6
7
8
9
10
*1
Shows "----" when a device is offline.
NOTE
• Inverters connected via CC-Link IE network are not recognized properly.
• The LED all-OFF setting and the connection check ON/OFF setting are available for direct connection of the FR-A800/FR-
F800 with the FR-A8NCG in it or the FR-E800-E.
• Those settings are enabled when online communication is established between the inverter and FR Configurator2.
• LEDs may not blink depending on the
Pr.1399
setting even when the connection check is enabled. Refer to the Instruction
Manual of the inverter for the details.
For use of the connection check ON/OFF setting
• Before using the connection check ON/OFF setting, check the setting of parameters in the following table.
Symbol
Name
Function and Description
A
All online
Set all the devices selected in the project to online.
B
Connection check LED all-OFF
• FR-A800/FR-F800 inverter with FR-A8NCG in it
Used to turn OFF the ACT LEDs on all successfully connected inverters.
• FR-E800-(SC)E
Used to stop the blinking of the NET LEDs on all successfully connected inverters.
C
St. No.
All the station numbers set in the project are displayed.
D
Connection status
Shows the connection status.
E
Switch online/offline
Switch from offline to online and from online to offline.
F
Operating status
Shows the operating status.
G
Operation command
Shows operation commands. Shows "----" if there is no start command.
H
Operation mode
Shows the operating mode.
I
Current warning
Shows the current warning. Shows "----" if there is no warning.
J
Error code
Shows if a connection error has occurred when the connection status is switched from offline
to online.
K
Connection check
ON
• FR-A800/FR-F800 inverter with FR-A8NCG in it
Used to turn ON the ACT LEDs on successfully connected inverters or plug-in options (FR-
A8NCG) to blink in the communication check of FR Configurator2. (The blinking LEDs will
automatically turn OFF five minutes after the start of blinking.)
• FR-E800-(SC)E
Used to turn ON the NET LEDs on successfully connected inverters to blink in the
communication check of FR Configurator2. (The blinking LEDs will automatically turn OFF
five minutes after the start of blinking.)
OFF
• FR-A800/FR-F800 inverter with FR-A8NCG in it
Used to turn OFF the ACT LEDs on successfully connected inverters or plug-in options (FR-
A8NCG) in the communication check of FR Configurator2.
• FR-E800-(SC)E
Used to stop the blinking of the NET LEDs on successfully connected inverters in the
communication check of FR Configurator2.
Model
Intermediate
device
Pr.
Name
Setting
FR-E800-(SC)E Not connected
1427
Ethernet function selection 1
Set "45237" in any of the parameters.
1428
Ethernet function selection 2
1429
Ethernet function selection 3
1430
Ethernet function selection 4