204
3. FUNCTION
3.14 Firmware update
3.14.7 Troubleshooting
Condition
Possible cause
Corrective action
The inverter is not detected by the
"Scan Network" function.
The IP address of the inverter is not specified.
Check the IP address of the inverter.
The IP address of the personal computer is not
specified.
Check the IP address of the personal computer.
The Ethernet cable is not connected or broken.
Connect or replace the Ethernet cable.
"Ethernet" cannot be selected in
"Select Ethernet Adapter" window.
The same IP address is used for the personal
computer and the inverter.
Check the IP address of the inverter.
The Ethernet cable is not connected or broken.
Connect or replace the Ethernet cable.
An error occurs when the network is
scanned.
When Ethernet is selected for the network adapter,
the Ethernet cable is not connected or the network
is scanned while the cable is broken.
Set a network adapter again.
Too many inverters are to be scanned.
Scan 512 or less inverters connected via
Ethernet.
An error occurs during firmware
update (inverter reset) via Ethernet
when multiple inverters are connected
in line topology.
The relay station is reset during firmware update
and the communication with the subsequent
inverters is disconnected.
Set the reset time longer to reset all the
connected inverters simultaneously.
An error occurs during firmware
update via Ethernet when multiple
inverters are connected.
For firmware update when multiple inverters are
connected, a communication delay occurs due to
relay delays.
Set the timeout time longer.
Firmware update fails.
The inverter power is OFF.
Update the firmware again.
USB or Ethernet connection is improper.
After firmware update of the FR-E800
series inverter failed, the firmware
cannot be updated again.
Power is supplied to the inverter from the USB port
or a 24 V external power supply, or the FR-
PU07BB.
Remove all the power sources and turn ON the
main circuit power supply, then update the
firmware again (after connecting the USB cable
for the update via a USB connector).