155
3. FUNCTION
3.7 Diagnostics
1
2
3
4
5
6
7
8
9
10
NOTE
• For EtherCAT communication, the main circuit capacitor's life cannot be measured during control using the controlword. To
measure the main circuit capacitor's life, disable the control using the controlword.
Procedure of main circuit capacitor life measuring
1.
The "Check before measurement" instructions are shown. Check the following items, and click [Next].
Motor is connected.
Motor is stopped.
2.
The "Preparation for measurement" instructions are shown. Set the operation mode in which parameters can be
written and click [Next].
Set
Pr.259 Main circuit capacitor life measuring
to "1".
3.
The "Power-OFF" instructions are shown. Turn OFF the inverter power, and click [Next].
4.
The "Power-ON" instructions are shown. After confirming that the power lamp is OFF, switch ON the inverter power
again, and click [Finish].
3.7.4
Diagnosis result output
Select [Diagnosis result output...] in the [Diagnose] menu to output the diagnosis data of the selected station and save the data
in a CSV text file.
[Diagnosis result output...] is also available in the pop-up menu. (Refer to
.)
3.7.5
Ethernet status
The Ethernet status check function is available for the following models.
Model: FR-A800-E, FR-F800-E, and FR-E700-NE
Click [Next].
Click [Next].
Click [Next].
Click [Finish].