4. TROUBLE INDICATION
4.1 Error code
0x90010101
Communication was not
established with the inverter
within the timeout time.
• Electromagnetic interference.
• Cable is damaged or broken.
• The personal computer port is set
invalid or the port is broken.
• The value in the network part of
the IP address is not the same
between the inverter and the
personal computer. (Ethernet
parameter setting)
• The communication driver failed
to open.
• FR-A800-E/F800-E/E800-E
The value set in
Pr.1432
Ethernet communication check
time interval
is too small.
• FR-E700-NE
The value set in
Pr.852 Ethernet
communication check time
interval
is too small.
• Reconnect or replace the cable.
• Activate the port using Device
Manager, or replace the port.
• Use the same value in the network
part of the IP address between the
inverter and the personal computer.
(Ethernet parameter setting)
• Establish the online connection.
• FR-A800-E/F800-E/E800-E
Set a larger value or "9999" in
Pr.1432 Ethernet communication
check time interval
.
• FR-E700-NE
Set a larger value or "9999" in
Pr.852 Ethernet communication
check time interval
.
• FR-A800-E/F800-E
The function to communicate with
FR Configurator2 is not set in
Pr.1427 to Pr.1429 Ethernet
function selection
.
• FR-A800-E-R2R
The function to communicate with
FR Configurator2 is not set in
Pr.1076 to Pr.1078 Ethernet
function selection
.
• FR-E800-E
The function to communicate with
FR Configurator2 is not set in
Pr.1427 to Pr.1430 Ethernet
function selection
.
• FR-E700-NE
The function to communicate with
FR Configurator2 is not set in
Pr.833 to Pr.835 Ethernet
function selection
.
"Ethernet" is selected from the "PC-side
port" drop-down list and "Not used" from the
"Through" drop-down list.
• FR-A800-E/F800-E
Set the combination of "5001" (or
"5002") and "45237" in any two of
Pr.1427 to Pr.1429
.
• FR-A800-E-R2R
Set the combination of "5001" (or
"5002") and "45237" in any two of
Pr.1076 to Pr.1078
.
• FR-E800-E
Set the combination of "5001" (or
"5002") and "45237" in any two of
Pr.1427 to Pr.1430
.
• FR-E700-NE
Set the combination of "31" (or "32")
and "20" in any two of
Pr.833 to
Pr.835
.
"GOT" is selected from the "Through" drop-
down list and the GOT and the inverter are
connected via Ethernet.
• FR-A800-E/F800-E
Set "5001", "5000", "5006", or
"5008" in any parameter from
Pr.1427 to Pr.1429
.
• FR-A800-E-R2R
Set "5001", "5000", "5006", or
"5008" in any parameter from
Pr.1076 to Pr.1078
.
• FR-E800-E
Set "5001", "5000", "5006", or
"5008" in any parameter from
Pr.1427 to Pr.1430
.
• FR-E700-NE
Set "31", "30", "36", or "38" in any
parameter from
Pr.833 to Pr.835
.
"Programmable controller" or "GOT to
programmable controller" is selected from
the "Through" drop-down list.
• FR-A800-E/F800-E
Set "5001" in any of
Pr.1427 to
Pr.1429
.
• FR-A800-E-R2R
Set "5001" in any of
Pr.1076 to
Pr.1078
.
• FR-E800-E
Set "5001" in any of
Pr.1427 to
Pr.1430
.
• FR-E700-NE
Set "31" in any of
Pr.833 to Pr.835
.
Error code (HEX)
Error message
Possible cause
Countermeasure