4. TROUBLE INDICATION
4.1 Error code
0x80010005
Because of incorrect wiring, data
was transmitted before
completing a data reception.
• The settings of
Pr.123 PU
communication waiting time
setting
and
Pr.337 RS-485
communication waiting time
setting
are too small.
• Electromagnetic interference.
• Cable breakage.
• Set a larger value or "9999" in
Pr.123 PU communication waiting
time setting
and
Pr.337 RS-485
communication waiting time
setting
.
• Set a larger value in
Pr.121 PU
communication retry count
and
Pr.335 RS-485 communication
retry count
.
• Replace the cable.
0x80010007
The inverter received an
unusable character (other than 0
to 9, A to F, or control codes).
• The
Pr.119 PU communication
stop bit length / data length
and
Pr.333 RS-485 communication
stop bit length / data length
settings are different with the
software settings.
• Electromagnetic interference.
• Cable breakage.
• Match the
Pr.119 PU
communication stop bit length /
data length
and
Pr.333 RS-485
communication stop bit length /
data length
settings with the
software settings.
• Set a larger value in
Pr.121 PU
communication retry count
and
Pr.335 RS-485 communication
retry count
.
• Replace the cable.
0x8001000A
A mode error occurred.
A test operation was attempted
without setting FR Configurator2 as
the operation (start) command
source, for example in the External
operation mode (EXT).
• Change the operation mode to the
PU operation mode (or NET).
• Check the setting values of
Pr.338
Communication operation
command source
,
Pr.550 NET
mode operation command source
selection
, and
Pr.551 PU mode
operation command source
selection
. (The operation command
source changes according to
inverter communication connection.
Refer to
.)
0x8001000C
Any value outside the setting
range cannot be written.
An out-of-range value or operation
frequency was written to the
parameter.
Set a value within the setting range,
and enter the setting.
If a writing error occurs even if a value
within the setting range is written,
check for the writing requirements for
each parameter. For the details on the
writing requirements, refer to the
Instruction Manual of the inverter.
0x80010011
The parameter outside the
setting range cannot be written.
An out-of-range value was written
to the parameter.
Set a value within the setting range,
and enter the setting.
If a writing error occurs even if a value
within the setting range is written,
check for the writing requirements for
each parameter. For the details on the
writing requirements, refer to the
Instruction Manual of the inverter.
0x80010012
A mode error occurred.
•
Pr.79 Operation mode
selection
is not set for PU/NET
(RS-485).
• A parameter or frequency setting
was attempted without setting FR
Configurator2 as such command
source, for example in the
External operation mode (EXT).
• Click [PU] button of Test Operation.
Change the setting of
Pr.79
for PU/NET
(RS-485).
• Change the operation mode to the
PU operation mode (or NET).
• Check the setting values of
Pr.339
Communication speed command
source
,
Pr.550 NET mode
operation command source
selection
, and
Pr.551 PU mode
operation command source
selection
. (The speed command
source changes according to
inverter communication connection.
Refer to
.)
0x80010013
No parameter can be written
during inverter running.
Parameter writing was attempted
during inverter operation.
Perform parameter writing after the
inverter is stopped.
Error code (HEX)
Error message
Possible cause
Countermeasure