Setting of operation mode of the inverter
• The inverter has three operation modes.
External operation mode: For giving a start command and a frequency command with an external potentiometer or
switches which are connected to the control circuit terminal.
PU operation mode: For giving a start command and a frequency command from the operation panel, parameter unit, or
RS-485 communication via the PU connector.
Network operation mode (NET operation mode): For giving a start command and a frequency command via the RS-485
terminals, a communication option, or the Ethernet connector.
*1
For the details of
Pr.79
, refer to the Instruction Manual of the inverter.
*2
Operation mode cannot be directly changed between the PU operation mode and Network operation mode.
• Controllability through communication
Refer to the following table to select the appropriate operation mode for the connection. Switching of the operation mode
is available using "test operation" (on
) or "parameter list" (on
) on the sub window. Refer to the Instruction
Manual (Detailed) of the inverter for details of each parameter.
Monitoring and parameter read can be performed from any operation regardless of the operation mode.
setting
Operation mode at power ON, at
power restoration, or after a reset.
Operation mode switchover
0 (initial value)
External operation mode
Switching among the External, PU, and NET operation modes is
enabled
1
PU operation mode
PU operation mode fixed.
2
External operation mode
Switching between the External and NET operation mode is
enabled.
Switching to PU operation mode is disabled.
3, 4
External/PU combined operation mode
Operation mode switching is disabled
6
External operation mode
Switching among the External, PU, and NET operation mode is
enabled while running.
7
X12 (MRS) signal ON...External
operation mode
Switching among the External, PU, and NET operation modes is
enabled
X12 (MRS) signal OFF...External
operation mode
External operation mode fixed. (Forcibly switched to External
operation mode.)
∗
When using USB connection, operation mode changing is available from FR Configurator2.
For the details of the operation mode switchover, refer to the Instruction Manual of the inverter.
Switching through the network
Switch to Network operation
mode through the network.
Press on
the PU to light
Press on
the PU to light
Switch to External
operation mode through
the network.
External operation
Switching with the PU
Press on the PU to light
Network operation
PU operation
Press on the PU to light
Network operation
When "0, 1 or 2" is set in
Pr. 340
Example: FR-A800
When "10 or 12" is set in
Pr. 340