Using the Developer function
The Developer function is not available for the following models.
Model: FR-CS80, FR-A700, FR-B (700), FR-B3 (700), FR-F700, FR-F700P, FR-E700, FR-D700, FR-E700EX, FR-D700-G,
and FR-E500
The Developer function becomes available when devices shown in the following table are connected.
Developer is used for creating sequence programs and writing them to the inverter to enable the use of the PLC function of the
inverter. PLC function is used for customizing inverter operation to meet the machine specifications. PLC function operates the
inverter according the input signals, or outputs signals and monitored values according to inverter operation. For details of
inverter settings related to the PLC function, refer to the PLC Function Programming Manual.
3.10.1 Before using Developer
When using Developer, enable the PLC function of the inverter (
Pr.414 PLC function operation selection
≠
0).
For details, refer to the Instruction Manual of the inverter used.
Outline of PLC function
• A800/F800
To enable the PLC function, set a value other than "0" in
Pr.414
. When
Pr.414
= "2 or 12", the sequence start (SQ) signal from
the external input terminal is valid regardless of the setting in
Pr.338 Communication operation command source
. (The
change of
Pr.414
setting is applied after an inverter reset.)
• E800
To enable the PLC function, set a value other than "0" in
Pr.414
. (The change of
Pr.414
setting is applied after an inverter
reset.)
Switch the execution key (RUN/STOP) of the sequence program by turning the SQ signal ON/OFF. The sequence program
can be executed by turning the SQ signal ON. To input the SQ signal, set "50" in any parameter from
Pr.178 to Pr.189 (Input
terminal function selection)
to assign the function to a terminal.
PC-side port
Intermediate
device
GOT
Programmable controller module
Model
OUT port
USB
No device
—
—
—
GOT
GOT2000/GOT1000 RS-232C/RS-485
—
Programmable
controller
—
—
CPU module
Ethernet
Not connected
—
—
—
Programmable
controller
—
—
CPU module / Ethernet module
COM port
Not connected
—
—
—
GOT
GOT1000
RS-232C/RS-485
—
Programmable
controller
—
—
CPU module (other than RCPU
module)
Pr.
Name
Initial
value
Setting
range
Description
414
PLC function operation
selection
0
0
PLC function disabled
1, 11
PLC function enabled
2, 12
Содержание MELSOFT FR Configurator2