26
1. OUTLINE
1.4 Connection and parameter setting
1.4
Connection and parameter setting
1.4.1
Connection method
For FR Configurator2, communication via a USB connector, a PU connector, the RS-485 terminal block, Ethernet, a GOT, or
a programmable controller is available. USB connection is initially selected. The inverter firmware can be updated using
Firmware Update Tool in the personal computer connected to the inverter via a USB connector or Ethernet. The inverter
firmware cannot be updated via a GOT or a programmable controller.
• USB connection (Refer to
Connect to USB connector (mini B connector) of the inverter. 1:1 connection is supported. Connection with using USB hub
is not supported.
• Serial communication (PU connector) (Refer to
.)
Connect to PU connector of the inverter. Serial port/RS-485 converter (cable) or USB/RS-485 converter (cable) is required.
• Ethernet connection (Ethernet connector / CC-Link IE Field Network Basic) (Refer to
Connection to the Ethernet connector of the inverter. Up to 120 inverters can be connected using a hub.
USB cable
Personal computer
(FR Configurator2)
Inverter
USB mini B
connector
USB connector
converter
Serial cable
Personal computer
(FR Configurator2)
Inverter
PU connector
RS-232C RS-485
Serial port
or
USB connector
converter
USB cable
Inverter
PU connector
USB RS-485
Ethernet
cable
Up to
120 inverters
Personal computer
(FR Configurator2)
Inverter
Ethernet
connector
Ethernet connector
Hub
Содержание MELSOFT FR Configurator2
Страница 7: ...6 MEMO ...
Страница 212: ...211 3 FUNCTION 3 15 Help 1 2 3 4 5 6 7 8 9 10 ...
Страница 213: ...212 3 FUNCTION 3 15 Help ...
Страница 214: ...213 CHAPTER 4 CHAPTER 4 4 5 6 7 8 9 10 TROUBLE INDICATION 4 1 Error code 214 ...