219
4. TROUBLE INDICATION
4.1 Error code
1
2
3
4
5
6
7
8
9
10
0x80010014
The setting value cannot be
written to the parameters to
which writing is prohibited.
• Writing is disabled by
Pr.77
Parameter write selection
.
(Pr.77 = "1 (write disabled)")
• Password lock is activated.
• Set
Pr.77 Parameter write
selection
to other than "1".
• Enter the password in
Pr.297
to
unlock password protection.
If an error occurs while Ethernet
parameters are set, change the
setting of the above parameter on the
operation panel.
0x80010016
Non-existed parameters cannot
be read or written.
• The version of the parameter file
in the setup software is different
from the inverter version.
• Simple mode is set by
Pr.160
User group read selection
.
• Password lock is activated.
• Parameter writing has been
attempted to
Pr.77 Parameter
write selection
or
Pr.79
Operation mode selection
in
the NET mode.
• The user attempted to read from
a read-protected parameter, or
write to a write-protected
parameter.
• The user attempted to perform
batch write to a set of parameters
that includes
Pr.77
.
• Reinstall the software.
• Change the setting of
Pr.160
to
choose a mode other than the
simple mode.
• Enter the password in
Pr.297
to
unlock the password lock.
• Change the setting of
Pr.77
or
Pr.79
on the operation panel.
• The user attempted to read from a
read-protected parameter, or write
to a write-protected parameter.
• The user attempted to perform batch
write to a set of parameters that
includes
Pr.77
.
0x80010017
The set option is not connected
to the inverter.
Reading of option parameter was
attempted while the option is not
installed.
Install the option to the inverter.
0x80010018
The bias and gain settings for an
analog value are too close.
There is only small difference
between the gain and bias settings
for an analog value.
Widen the gap between the gain and
bias settings for an analog value.
0x8001001A
An unsupported model is
connected.
Please contact your sales representative.
0x80010021
The mode cannot be switched
during inverter running.
Change the operation mode after
the inverter stops.
• Set
Pr.77 Parameter write
selection
to "2".
• Stop the inverter.
0x80010022
While the forward rotation
command (STF) is ON, the
operation mode cannot be
switched to the External
operation mode.
Switching to the External mode
was attempted while the forward
rotation signal (STF) is ON.
Change the operation mode after
switching STF to OFF.
0x80010023
While the reverse rotation
command (STR) is ON, the
operation mode cannot be
switched to the External
operation mode.
Switching to the External mode
was attempted while the reverse
rotation signal (STR) is ON.
Change the operation mode after
switching STR to OFF.
0x80010024
The mode cannot be switched
during the present operation
mode.
The operation mode was
attempted to be switched to the
mode other than the one selected
by
Pr.79 Operation mode
selection
.
Change the setting of
Pr.79
Operation mode selection
.
0x80010025
The inverter cannot be reset with
the present setting.
Reset is disabled by
Pr.75 Reset
selection/disconnected PU
detection/PU stop selection
.
Change the setting of
Pr.75 Reset
selection/disconnected PU
detection/PU stop selection
.
0x80010026
An unexpected error occurred in
S/W.
Please contact your sales representative.
0x80010027
The remote password contains
invalid characters.
Invalid characters were entered in
the remote password.
Eliminate the invalid characters.
0x80010028
The remote password protection
is still active.
A remote password is set for a
device connected via Ethernet, but
the password has not been
entered.
Enter the correct password.
Error code (HEX)
Error message
Possible cause
Countermeasure