32
1. OUTLINE
1.4 Connection and parameter setting
FR-E700 and FR-E700EX
• Applicable cable
Related parameters for USB connection
Set the following communication parameter when connecting the USB connector of the inverter. To set parameters or input
operation commands, set the following parameters and switch the operation mode to PU operation mode.
NOTE
• Set a station number of each inverter in
Pr.547 USB communication station number
. Perform inverter reset after setting the
parameter.
Interface
Conforms to USB 1.1
Transmission speed
12 Mbps
Wiring length
Maximum 5 m
Connector
800 series, FR-E700, and FR-E700EX
USB mini B connector (receptacle)
FR-A700, FR-B (700), and FR-B3 (700) USB B connector (B receptacle)
Recommended USB cable
MR-J3USBCBL3M (cable length 3 m)
Inverter
Parameter setting
Operation
mode
Communication parameter
Command source parameter
FR-A800(-E)
FR-B
FR-B3
FR-B4
FR-F800(-E)
FR-E800(-E/-SCE)
Pr.548 USB communication check time
interval
= "9999" (initial value)
Pr.551 PU mode operation
command source selection
= "3 or
9999" (initial value: "9999")
PU
FR-A700
FR-E700(SC)(NC)
FR-E700EX
Pr.548 USB communication check time
interval
≠
"0" (initial value: "9999")
Pr.551 PU mode operation
command source selection
= "3 or
9999" (initial value: "9999")
FR-B (700)
FR-B3 (700)
Pr.551 PU mode operation
command source selection
= "3"
(initial value: "2")
USB cable
USB connector
How to open the USB connector cover
Pull the cover in the direction of arrow.
Then turn it upward.