Learning Basic Features
Basic HAND/AUTO/OFF Mode Operations
Mode
Description
HAND Mode
(Locally
controlled
operation mode)
In HAND mode, operation is available only by the keypad input. In Monitor
mode, the currently set frequency reference is displayed at all times.
Also, in HAND mode:
•
The first monitoring item is used to adjust the frequency with the up/down
and left/right keys. The set frequency is reflected in DRV-02 (HAND Cmd
Freq).
•
The motor’s rotation direction can be set at DRV-02 (Keypad Run Dir).
•
Terminal block functions do not operate (with the exception of BX, External
Trip, and multi-step acc/dec operation related terminal functions).
•
Fire mode commands take the highest priority (if any are given).
•
The following advanced features are not available:
-
PID / EPID control
-
Flow compensation
-
Pump clean
-
Load tuning
-
Motor preheating
-
Time scheduling
-
PowerOn resume
-
Multiple motor control
•
Inverter monitoring and protection features are available in HAND mode.
OFF Mode
(Standby)
In OFF mode, the inverter operation stops. Pressing the OFF key during
HAND/AUTO mode operations will cause the OFF LED to turn on. Then, the
inverter stops operating or decelerates and stops, according to the deceleration
options set by the user.
Also, in AUTO mode:
•
Terminal block functions do not operate (with the exception of BX, External
Trip and multi-step acc/dec operation related terminal functions).
•
Fire mode commands take the highest priority (if any are given).
AUTO Mode
(Remotely
controlled
operation mode)
In AUTO mode, the inverter operates based on the command from the
command source set at DRV-06 (Cmd Source), with the frequency reference from
the source set at DRV-07 (Freq Ref Src).
Содержание 6731001500
Страница 1: ......
Страница 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500kW 3 Phase ...
Страница 34: ...21 Installing the Inverter 400 V 220 500kW ...
Страница 37: ...Installing the Inverter 24 3 Remove the keypad from the inverter body 0 75 30kWModels 37 90kWModels ...
Страница 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Страница 66: ...Perform BasicOperations 53 ...
Страница 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Страница 107: ...94 Learning BasicFeatures ...
Страница 129: ...116 Learning BasicFeatures second to 0 01 second will resultin amodified acceleration time of 60 00 seconds ...
Страница 151: ...138 Learning BasicFeatures Group Code Name LCDDisplay ParameterSetting SettingRange Unit frequency ...
Страница 187: ...174 Learning Advanced Features PIDCommandBlock ...
Страница 188: ...175 Learning Advanced Features ...
Страница 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Страница 190: ...177 Learning Advanced Features PIDOutputBlock ...
Страница 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Страница 205: ...192 Learning Advanced Features EPID1Controlblock ...
Страница 206: ...193 Learning Advanced Features EPID2Controlblock ...
Страница 228: ...215 Learning Advanced Features ...
Страница 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Страница 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Страница 363: ...350 Learning Protection Features Fan life examination isonlyfor the reference and cannot be used asan absolute value ...
Страница 404: ...391 RS 485 Communication Features B3 4th motor running B2 3rd motor running B1 2nd motor running B0 1st motor running ...
Страница 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Страница 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Страница 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Страница 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Страница 588: ...575 Troubleshooting ...
Страница 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Страница 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Страница 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Страница 643: ...630 ...
Страница 644: ...631 ...
Страница 645: ...632 ...