Learning Advanced Features
5.44.1
Multiple Motor Control (MMC) Basic Sequence
Multiple motor control (MMC) is an operation based on PID control. During an MMC operation,
the main and auxiliary motors organically operate together.
During a PID operation, the auxiliary motors are turned on when the inverter frequency reaches
the start frequencies set at AP1-61–65 (Start freq), and the difference between the PID reference
and feedback is bigger than the value set at AP1-50. Then, the auxiliary motors stop operating
when the operation frequency reach the stop frequency set at AP1-70–74 (Stop Freq 1–5) and the
difference between the PID feedback and reference becomes greater than the value set at AP1-50.
AP1-51 Acc Time
AP1-52 Dec Time
Parameters used when AP1-40 is set to ‘Single Ctrl’
When an auxiliary motor starts or stops, the main motor stops the
PID control, and performs general acceleration and deceleration.
When an auxiliary motor starts, the main motor decelerates to the
auxiliary motor deceleration frequency set at AP1-70–74 (Stop Freq
1–5) based on the deceleration time set at AP1-52 (Dec Time).
When the auxiliary motor stops, the main motor accelerates up to
the auxiliary motor restart frequency set at AP1-61–65 (Start Freq 1–
5) based on the acceleration time set at AP1-51 (Acc Time).
AP1-53 Aux Start DT
AP1-54 Aux Stop DT
The auxiliary motors turns on or off after the auxiliary motor stop
delay time or the auxiliary motor restart delay time elapses, or if the
difference between the current reference and the feedback is greater
than the value set at AP1-50 (Actual Pr Diff).
AP1-61–65 Start Freq1–5
Sets the auxiliary motor start frequency.
AP1-70–74 Stop Freq 1–5
Sets the auxiliary motor stop frequency.
AP1-95 AuxRunTime Sel
Selects auxiliary motor to be used in AP1-96 and AP1-97.
AP1-96 AuxRunTime Day
Indicates operating time(day) selected in AP1-95.
AP1-97 AuxRunTime Min
Indicates operating time of auxiliary motors selected in AP1-95.
AP1-98 AuxRunTime Clr
Deletes operating time of auxiliary motors.
OUT-31–35 Relay 1–5
OUT-36 Q1 Define
Configure the output terminals to ’21 (MMC)’ to use the terminals to
control the auxiliary motors. The number of the configured output
terminals determines the total number of auxiliary motors to be
used.
Содержание 6731001500
Страница 1: ......
Страница 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500kW 3 Phase ...
Страница 34: ...21 Installing the Inverter 400 V 220 500kW ...
Страница 37: ...Installing the Inverter 24 3 Remove the keypad from the inverter body 0 75 30kWModels 37 90kWModels ...
Страница 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Страница 66: ...Perform BasicOperations 53 ...
Страница 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Страница 107: ...94 Learning BasicFeatures ...
Страница 129: ...116 Learning BasicFeatures second to 0 01 second will resultin amodified acceleration time of 60 00 seconds ...
Страница 151: ...138 Learning BasicFeatures Group Code Name LCDDisplay ParameterSetting SettingRange Unit frequency ...
Страница 187: ...174 Learning Advanced Features PIDCommandBlock ...
Страница 188: ...175 Learning Advanced Features ...
Страница 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Страница 190: ...177 Learning Advanced Features PIDOutputBlock ...
Страница 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Страница 205: ...192 Learning Advanced Features EPID1Controlblock ...
Страница 206: ...193 Learning Advanced Features EPID2Controlblock ...
Страница 228: ...215 Learning Advanced Features ...
Страница 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Страница 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Страница 363: ...350 Learning Protection Features Fan life examination isonlyfor the reference and cannot be used asan absolute value ...
Страница 404: ...391 RS 485 Communication Features B3 4th motor running B2 3rd motor running B1 2nd motor running B0 1st motor running ...
Страница 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Страница 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Страница 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Страница 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Страница 588: ...575 Troubleshooting ...
Страница 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Страница 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Страница 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Страница 643: ...630 ...
Страница 644: ...631 ...
Страница 645: ...632 ...