90
Learning Basic Features
terminal. Use voltage inputs ranging from 0–10 V (unipolar) for forward only operation. Use
voltage inputs ranging from -10 to +10 V (bipolar) for both directions, where negative voltage
inputs are used in reverse operations.
4.2.3.1
Setting a Frequency Reference for 0–10 V Input
Set IN-06 (V1 Polarity) to ‘0 (unipolar)’. Use a voltage output from an external source or use the
voltage output from the VR terminal to provide inputs to V1. Refer to the diagrams below for the
wiring required for each application.
[External source application]
[Internal source (VR) application]
Group Code
Name
LCD Display
Parameter Setting Setting Range
Unit
DRV
07
Frequency reference
source
Freq Ref Src
2
V1
0–11
-
IN
01
Frequency at
maximum analog
input
Freq at
100%
Maximum
frequency
0.00–
Max.
Frequency
Hz
05
V1 input monitor
V1
Monitor[V]
0.00
0.00–12.00
V
06
V1 polarity options
V1 Polarity
0
Unipolar
0–1
-
07
V1 input filter time
constant
V1 Filter
10
0–10000
msec
08
V1 minimum input
voltage
V1 volt x1
0.00
0.00–10.00
V
09
V1 output at
minimum voltage
(%)
V1 Perc y1
0.00
0.00–100.00
%
10
V1 maximum input
voltage
V1 Volt x2
10.00
0 .00– 12.00
V
11
V1 output at
maximum voltage
V1 Perc y2
100.00
0–100
%
V1
CM
VR
V1
CM
Содержание 6731001500
Страница 1: ......
Страница 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500kW 3 Phase ...
Страница 34: ...21 Installing the Inverter 400 V 220 500kW ...
Страница 37: ...Installing the Inverter 24 3 Remove the keypad from the inverter body 0 75 30kWModels 37 90kWModels ...
Страница 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Страница 66: ...Perform BasicOperations 53 ...
Страница 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Страница 107: ...94 Learning BasicFeatures ...
Страница 129: ...116 Learning BasicFeatures second to 0 01 second will resultin amodified acceleration time of 60 00 seconds ...
Страница 151: ...138 Learning BasicFeatures Group Code Name LCDDisplay ParameterSetting SettingRange Unit frequency ...
Страница 187: ...174 Learning Advanced Features PIDCommandBlock ...
Страница 188: ...175 Learning Advanced Features ...
Страница 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Страница 190: ...177 Learning Advanced Features PIDOutputBlock ...
Страница 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Страница 205: ...192 Learning Advanced Features EPID1Controlblock ...
Страница 206: ...193 Learning Advanced Features EPID2Controlblock ...
Страница 228: ...215 Learning Advanced Features ...
Страница 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Страница 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Страница 363: ...350 Learning Protection Features Fan life examination isonlyfor the reference and cannot be used asan absolute value ...
Страница 404: ...391 RS 485 Communication Features B3 4th motor running B2 3rd motor running B1 2nd motor running B0 1st motor running ...
Страница 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Страница 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Страница 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Страница 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Страница 588: ...575 Troubleshooting ...
Страница 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Страница 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Страница 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Страница 643: ...630 ...
Страница 644: ...631 ...
Страница 645: ...632 ...