306
Learning Advanced Features
Voltage and Current Analog Output Setting Details
5.47.2
Analog Pulse Output
Output item selection and pulse size adjustment can be made for the TO (Pulse Output) terminal.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
OUT
61
Pulse output setting
TO Mode
0 Frequency
0–15
-
62
Pulse output gain
TO Gain
100.0
-1000.0–
1000.0
-
63
Pulse output bias
TO Bias
1000.0
-100.0–100.0
-
64
Pulse output filter
TO Filter
5
0–10000
-
65
Pulse output constant
output2
TO Const %
0.0
0.0–100.0
%
66
Pulse output monitor TO Monitor
0.0
0–1000.0
%
Analog Pulse Output Setting Details
Code
Description
OUT-62 TO Gain, OUT-
63 TO Bias
Adjusts output value and offset. If frequency is selected as an output, it will
operate as shown below.
C2
34567589:
;<=3456
C2 ><?8 @ C2 A?<B
The following graph illustrates that the pulse output (TO) changes depend
on OUT-62 (TO Gain) and OUT-63 (TO Bias) values. The Y-axis is an analog
output current (0–32 kHz), and X-axis is a % value of the output item.
For example, if the maximum frequency set at DRV-20 (Max Freq) is 60 Hz
and present output frequency is 30 Hz, then the x-axis value on the next
Monitor
percentage (%) with 10 V as the standard.
Содержание 6731001500
Страница 1: ......
Страница 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500kW 3 Phase ...
Страница 34: ...21 Installing the Inverter 400 V 220 500kW ...
Страница 37: ...Installing the Inverter 24 3 Remove the keypad from the inverter body 0 75 30kWModels 37 90kWModels ...
Страница 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Страница 66: ...Perform BasicOperations 53 ...
Страница 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Страница 107: ...94 Learning BasicFeatures ...
Страница 129: ...116 Learning BasicFeatures second to 0 01 second will resultin amodified acceleration time of 60 00 seconds ...
Страница 151: ...138 Learning BasicFeatures Group Code Name LCDDisplay ParameterSetting SettingRange Unit frequency ...
Страница 187: ...174 Learning Advanced Features PIDCommandBlock ...
Страница 188: ...175 Learning Advanced Features ...
Страница 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Страница 190: ...177 Learning Advanced Features PIDOutputBlock ...
Страница 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Страница 205: ...192 Learning Advanced Features EPID1Controlblock ...
Страница 206: ...193 Learning Advanced Features EPID2Controlblock ...
Страница 228: ...215 Learning Advanced Features ...
Страница 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Страница 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Страница 363: ...350 Learning Protection Features Fan life examination isonlyfor the reference and cannot be used asan absolute value ...
Страница 404: ...391 RS 485 Communication Features B3 4th motor running B2 3rd motor running B1 2nd motor running B0 1st motor running ...
Страница 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Страница 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Страница 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Страница 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Страница 588: ...575 Troubleshooting ...
Страница 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Страница 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Страница 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Страница 643: ...630 ...
Страница 644: ...631 ...
Страница 645: ...632 ...