290
Learning Advanced Features
5.44.5
Aux Motor Time Change
It is used to set a motor to the smallest number among Drives not inter-locked by [AP1-43 Starting
Aux] and place others in order based on it when operating time of every motor is deleted through
<1:All> of [AP1-98 AuxRunTime Clr].
In case that operating time of each motor is deleted through <2: Aux1> ~ <6: Aux5> of [AP1-98
AuxRunTime Clr] or changed by combining [AP1-96 AuxRunTime Day] and [AP1-97 AuxRunTime
Min], motor stopped changes the priority with motor stopped as operating motor does with
operating motor.
The table below shows the case to change the operating time of Aux Motor2 running on the same
condition of Sequence1.
Sequences
Aux Priority 1
(Operating
time: min)
Aux Priority 2
(Operating
time: min)
Aux Priority 3
(Operating
time: min)
Aux Priority 4
(Operating
time: min)
Aux Priority 5
(Operating
time: min)
1
Aux Motor3
(00:30)
<Operating>
Aux Motor2
(00:40)
<Operating>
Aux Motor1
(00:50)
<Operating>
Aux Motor4
(01:30)
<Operating>
Aux Motor 5
(01:50)
<Operating>
Set <3 Aux2of [AP1-98 AuxRunTime Clr]
2
Aux Motor2
(00:00)
<Operating>
Aux Motor3
(00:30)
<Operating>
Aux Motor1
(00:50)
<Operating>
Aux Motor4
(01:30)
<Operating>
Aux Motor 5
(01:50)
<Operating>
Set time of Aux2to 2:00 through [AP1-97 AuxRunTime Min]
3
Aux Motor3
(00:30)
<Operating>
Aux Motor1
(00:50)
<Operating>
Aux Motor2
(02:00)
<Operating>
Aux Motor4
(01:30)
<Stopping>
Aux Motor 5
(01:50)
< Stopping >
The table below shows the case to change the operating time of Aux Motor5 stopped on the
same condition of Sequence1
Sequences
Aux Priority 1
(Operating
time: min)
Aux Priority 2
(Operating
time: min)
Aux Priority 3
(Operating
time: min)
Aux Priority 4
(Operating
time: min)
Aux Priority 5
(Operating
time: min)
1
Aux Motor3
(00:30)
<Operating>
Aux Motor2
(00:40)
<Operating>
Aux Motor1
(00:50)
<Operating>
Aux Motor4
(01:30)
<Stopping>
Aux Motor 5
(01:50)
<Stopping>
Set <6: Aux5> of [AP1-98 AuxRunTime Clr]
2
Aux Motor3
(00:30)
<Operating>
Aux Motor2
(00:40)
<Operating>
Aux Motor1
(00:50)
<Operating>
Aux Motor 5
(0)
<Stopping>
Aux Motor 4
(01:30)
<Stopping>
Set time of Aux5 to 2:00 through [AP1-97 AuxRunTime Min]
3
Aux Motor3
(00:30)
<Operating>
Aux Motor2
(00:40)
<Operating>
Aux Motor1
(00:50)
<Operating>
Aux Motor4
(01:30)
<Stopping>
Aux Motor 5
(02:00)
<Stopping>
Содержание 6731001500
Страница 1: ......
Страница 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500kW 3 Phase ...
Страница 34: ...21 Installing the Inverter 400 V 220 500kW ...
Страница 37: ...Installing the Inverter 24 3 Remove the keypad from the inverter body 0 75 30kWModels 37 90kWModels ...
Страница 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Страница 66: ...Perform BasicOperations 53 ...
Страница 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Страница 107: ...94 Learning BasicFeatures ...
Страница 129: ...116 Learning BasicFeatures second to 0 01 second will resultin amodified acceleration time of 60 00 seconds ...
Страница 151: ...138 Learning BasicFeatures Group Code Name LCDDisplay ParameterSetting SettingRange Unit frequency ...
Страница 187: ...174 Learning Advanced Features PIDCommandBlock ...
Страница 188: ...175 Learning Advanced Features ...
Страница 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Страница 190: ...177 Learning Advanced Features PIDOutputBlock ...
Страница 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Страница 205: ...192 Learning Advanced Features EPID1Controlblock ...
Страница 206: ...193 Learning Advanced Features EPID2Controlblock ...
Страница 228: ...215 Learning Advanced Features ...
Страница 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Страница 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Страница 363: ...350 Learning Protection Features Fan life examination isonlyfor the reference and cannot be used asan absolute value ...
Страница 404: ...391 RS 485 Communication Features B3 4th motor running B2 3rd motor running B1 2nd motor running B0 1st motor running ...
Страница 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Страница 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Страница 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Страница 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Страница 588: ...575 Troubleshooting ...
Страница 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Страница 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Страница 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Страница 643: ...630 ...
Страница 644: ...631 ...
Страница 645: ...632 ...