223
Learning Advanced Features
Time Event function enables the user to operate the inverter using the RTC (Real-Time Clock)
feature at certain times that the user would like to set. An RTC battery is installed on the I/O board
of the H100 inverter, and it lasts approximately 25,800 hours with the inverter turned off, and
53,300 hours with the inverter turned on.
To use the Time Event, set the current date and time. Three parameters need to be set to configure
the Time event feature: Time Period Module, Time Event, and Exception Date.
Time Period
Description
Time Period
Used to set the time of operation.
Time Event
Used to set the time of operation.
Exception Date
Used to specify the exception date. Exception date has the highest priority.
4 Time period Module types, 8 Time Event Module types, and 8 Exception day types can be used
to configure time events. The Time Event function works based on a series of configuration using
the modules listed in the table above.
Group Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
AP3
01
Current date
Now Date
01/01/2000
01/01/2000 ~
12/31/2099 (Date)
Hz
02
Current time
Now Time
0: 00
0: 00–23: 59
Sec
03
Current day of
the week
Now
Weekday
0000001
0000000–1111111
-
04
Summer Time
Start date
Summer T
Start
04/01
01/01 ~ Summer T
Stop
Day
05
Summer Time
Finish date
Summer T
Stop
11/31
Summer T Start ~
12/31(Date)
Day
10
Period
connection
status
Period Status -
-
-
11
Time Period 1
Start time
Period1
StartT
24: 00
00:00 ~ 24:00
Min
12
Time Period 1
End time
Period1 Stop
T
24: 00
Period1 StartT ~
24:00(Min)
Min
13
Time Period 1
Day of the week
Period1 Day
0000000
0000000~1111111
-
14
Time Period 2
Period2
24: 00
00:00 ~ 24:00
Min
Содержание 6731001500
Страница 1: ......
Страница 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500kW 3 Phase ...
Страница 34: ...21 Installing the Inverter 400 V 220 500kW ...
Страница 37: ...Installing the Inverter 24 3 Remove the keypad from the inverter body 0 75 30kWModels 37 90kWModels ...
Страница 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Страница 66: ...Perform BasicOperations 53 ...
Страница 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Страница 107: ...94 Learning BasicFeatures ...
Страница 129: ...116 Learning BasicFeatures second to 0 01 second will resultin amodified acceleration time of 60 00 seconds ...
Страница 151: ...138 Learning BasicFeatures Group Code Name LCDDisplay ParameterSetting SettingRange Unit frequency ...
Страница 187: ...174 Learning Advanced Features PIDCommandBlock ...
Страница 188: ...175 Learning Advanced Features ...
Страница 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Страница 190: ...177 Learning Advanced Features PIDOutputBlock ...
Страница 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Страница 205: ...192 Learning Advanced Features EPID1Controlblock ...
Страница 206: ...193 Learning Advanced Features EPID2Controlblock ...
Страница 228: ...215 Learning Advanced Features ...
Страница 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Страница 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Страница 363: ...350 Learning Protection Features Fan life examination isonlyfor the reference and cannot be used asan absolute value ...
Страница 404: ...391 RS 485 Communication Features B3 4th motor running B2 3rd motor running B1 2nd motor running B0 1st motor running ...
Страница 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Страница 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Страница 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Страница 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Страница 588: ...575 Troubleshooting ...
Страница 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Страница 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Страница 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Страница 643: ...630 ...
Страница 644: ...631 ...
Страница 645: ...632 ...