Learning Advanced Features
Code
Description
AP1-58 Auto Op Time
Indicates time to activate Auto Change. In case that other conditions for
Auto Change are not met in spite of meeting the condition of AP1-56,
the value of time in AP1-58 might be bigger than the value set at Auto
Ch Time of AP1-56 because of the failure of Auto Change.
When
AP1-55 (Auto Ch Mode) is set to ‘
0 (None),’ the auxiliary motors operates based on the order
(sequence) set at AP1-43 (Starting Aux). Auto Change functionality is disabled.
When
AP1-55 (Auto Ch Mode) is set to ‘1
(Aux Exchange)’, the auxiliary motors operate based on the
order (sequence) set at AP1-43 (Starting Aux). Auto Change is activated when auxiliary motors
are in the operating state over time of AP1-56 and then every auxiliary motor is stopped.
Once the auto change is operated, the auxiliary motor that started first is given the lowest priority
and all the other auxiliary motors’ priority level increases by 1. Then, general MMC operation
continues.
NOTE
Auto change does not work while the auxiliary motors are operating. Auto change is operated only
when all the auxiliary motors are stopped and if all the conditions set for the auto change are met.
When the inverter stops, all motors stop operating, and the auxiliary motor with the highest priority
becomes the starting auxiliary motor. If the inverter power is turned off then turned back on, the
auxiliary motor set at AP1-43 (Starting Aux) becomes the starting auxiliary motor.
Start order and stop order of the auxiliary motors are based on the order set at AP1-49 (FIFO/FILO).
The following diagrams depict the auxiliary motor start and stop sequence, based on a FIFO
configuration, when the inverter operation time exceeds the auto change interval set at AP1-58. If all
the auxiliary motors are turned off and the inverter operation frequency is below the frequency set at
AP1-58 (Auto Op Time), auto change is operated. Then, when the inverter frequency increases due to
decrease in the feedback, auxiliary motor #2 starts instead of auxiliary motor #1 due to this auto
change (auxiliary motor #1 starts last, for it has the lowest priority).
Later on during the operation, when the feedback increases and the auxiliary motors begin to stop,
the FILO setting is applied to control the order for the auxiliary motors to stop.
Содержание 6731001500
Страница 1: ......
Страница 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500kW 3 Phase ...
Страница 34: ...21 Installing the Inverter 400 V 220 500kW ...
Страница 37: ...Installing the Inverter 24 3 Remove the keypad from the inverter body 0 75 30kWModels 37 90kWModels ...
Страница 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Страница 66: ...Perform BasicOperations 53 ...
Страница 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Страница 107: ...94 Learning BasicFeatures ...
Страница 129: ...116 Learning BasicFeatures second to 0 01 second will resultin amodified acceleration time of 60 00 seconds ...
Страница 151: ...138 Learning BasicFeatures Group Code Name LCDDisplay ParameterSetting SettingRange Unit frequency ...
Страница 187: ...174 Learning Advanced Features PIDCommandBlock ...
Страница 188: ...175 Learning Advanced Features ...
Страница 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Страница 190: ...177 Learning Advanced Features PIDOutputBlock ...
Страница 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Страница 205: ...192 Learning Advanced Features EPID1Controlblock ...
Страница 206: ...193 Learning Advanced Features EPID2Controlblock ...
Страница 228: ...215 Learning Advanced Features ...
Страница 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Страница 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Страница 363: ...350 Learning Protection Features Fan life examination isonlyfor the reference and cannot be used asan absolute value ...
Страница 404: ...391 RS 485 Communication Features B3 4th motor running B2 3rd motor running B1 2nd motor running B0 1st motor running ...
Страница 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Страница 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Страница 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Страница 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Страница 588: ...575 Troubleshooting ...
Страница 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Страница 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Страница 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Страница 643: ...630 ...
Страница 644: ...631 ...
Страница 645: ...632 ...