Learning Advanced Features
Code
Description
OUT-01 AO1
Mode
Select a constant value for output. The following example for output voltage
setting.
Setting
Function
0
Frequency Outputs operation frequency as a standard. 10 V output is
made from the frequency set at DRV-20 (Max Freq).
1
Output
Current
10 V output is made from 150% of inverter rated current.
2
Output
Voltage
Sets the outputs based on the inverter output voltage. 10 V
output is made from a set voltage in BAS-15 (Rated V).
If 0 V is set in BAS-15, 200 V/400 V models output
10 V based on the actual input voltages (240 V and 480 V
respectively).
3
DC Link
Volt
Outputs inverter DC link voltage as a standard.
Outputs 10 V when the DC link voltage is 410 V DC for 200 V
models, and 820 V DC for 400 V models.
4
Output
Power
Monitors output wattage. 150% of rated output is the
maximum display voltage (10 V).
7
Target
Freq
Outputs set frequency as a standard. Outputs 10 V at the
maximum frequency (DRV-20).
8
Ramp
Freq
Outputs frequency calculated with Acc/Dec function as a
standard. May vary with actual output frequency. Outputs 10 V.
9
PID Ref
Value
Outputs command value of a PID controller as a standard.
Outputs approximately 6.6 V at 100%.
10 PID Fdk
Value
Outputs feedback volume of a PID controller as a standard.
Outputs approximately 6.6 V at 100%.
11 PID
Output
Outputs output value of a PID controller as a standard. Outputs
approximately 10 V at 100%.
12 Constant
Outputs OUT-05 (AO1 Const %) value as a standard.
13 EPID1
Output
Output is based on the output value of the external PID1
controller. Outputs 10 V in 100%.
Содержание 6731001500
Страница 1: ......
Страница 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500kW 3 Phase ...
Страница 34: ...21 Installing the Inverter 400 V 220 500kW ...
Страница 37: ...Installing the Inverter 24 3 Remove the keypad from the inverter body 0 75 30kWModels 37 90kWModels ...
Страница 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Страница 66: ...Perform BasicOperations 53 ...
Страница 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Страница 107: ...94 Learning BasicFeatures ...
Страница 129: ...116 Learning BasicFeatures second to 0 01 second will resultin amodified acceleration time of 60 00 seconds ...
Страница 151: ...138 Learning BasicFeatures Group Code Name LCDDisplay ParameterSetting SettingRange Unit frequency ...
Страница 187: ...174 Learning Advanced Features PIDCommandBlock ...
Страница 188: ...175 Learning Advanced Features ...
Страница 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Страница 190: ...177 Learning Advanced Features PIDOutputBlock ...
Страница 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Страница 205: ...192 Learning Advanced Features EPID1Controlblock ...
Страница 206: ...193 Learning Advanced Features EPID2Controlblock ...
Страница 228: ...215 Learning Advanced Features ...
Страница 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Страница 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Страница 363: ...350 Learning Protection Features Fan life examination isonlyfor the reference and cannot be used asan absolute value ...
Страница 404: ...391 RS 485 Communication Features B3 4th motor running B2 3rd motor running B1 2nd motor running B0 1st motor running ...
Страница 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Страница 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Страница 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Страница 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Страница 588: ...575 Troubleshooting ...
Страница 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Страница 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Страница 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Страница 643: ...630 ...
Страница 644: ...631 ...
Страница 645: ...632 ...