ID
Index Name
Value
Unit
Description
2851
8
TCritical
10
s
Max. permissible time at low speed and
nominal pressure
2851
9
iGearPump
-1
Gear ratio between pump and motor
2851
10
p0
20
bar
Max. permissible stationary pressure at a
standstill
Table 7.99: Pump data settings (continue)
The position and speed actual values are evaluated via the encoder inputs for
position and speed. In this example, an SSI linear encoder is used which must be
set to CH1(1) = X7 (e.g. SinCos, channel 1) via the function selector in the encoder
screen.
NOTE
l
The encoder for commutation and torque control as well as speed
control are used for the motor.
l
The encoder for position control is used for cylinder-position and
cylinder-speed control.
ID No.: 0842.26B.5-01 Date: 09.2020
ServoOne - Device Help
218
7 Control
Image 7.92: “Encoder selection” screen
In addition, the encoder must also be configured under Options. Here, the encoder
type can be set under “Cyclic position via” and the absolute value interface of the
respective encoder.