www.jps.com.tw
41
10.5 Analog Output Group
【NOTE】 The output signal of AM1is used to drive the external analog meter. The rating of meter is 1V/1mA.
z
Pr.370
Î
AMOUT-Select Data
Value
Description
0
No output.
1
Output Frequency.
2
Output Current
3
Output Voltage
4
Motor’s Actual Speed
5~9 Reserved.
10
100% Test Output.
11
75% Test Output.
12
50% Test Output.
13
25% Test Output.
14
12.5% Test Output.
【NOTE】
All these 5 functions are used to adjust the
linearity of AM1 output. Normally, the
linearity had been adjusted in factory already;
therefore, users don’t have to do it again.
15
The output of AM1 is set by Pr.372.
Description:
Select =0
Æ
AM1 has no output.
Select =1
Æ
The output of AM1 presents the driver’s output frequency. The accuracy is 0.01Hz.
Select =2
Æ
The output of AM1 presents the driver’s output current. The accuracy is 0.1A.
Select =3
Æ
The output of AM1 presents the driver’s output voltage. The accuracy is 1V.
Select =4
Æ
The output of AM1 presents the motor’s actual speed. The accuracy is 1rpm.
Select =5~9
Æ
All these are reserved. Should not select these function numbers for operation safety.
Select =10
Æ
AM1 send out 100% volume for adjusting. The output is adjusted by Pr.373.
Select =11
Æ
AM1 send out 75% volume for adjusting. The output is adjusted by Pr.374.
Select =12
Æ
AM1 send out 50% volume for adjusting. The output is adjusted by Pr.375.
Select =13
Æ
AM1 send out 25% volume for adjusting. The output is adjusted by Pr.376.
Select =14
Æ
AM1 send out 12.5% volume for adjusting. The output is adjusted by Pr.377.
Select =15
Æ
The output of AM1 is set by Pr.372.
【NOTE】After change this parameter, the driver should be reset to let the changes be effect.