10.7 IMSV Motor Group
z
Pr.116
Î
Motor Pole No.
According to the data of the motor’s manufacturer, set correct value.
z
Pr.198
Î
Motor Ke(Back Emf constant)
When Motor running at 1000rpm,input Pr.13 value to this parameter。
z
Pr.202
Î
No-Load Speed (=Base or Synchrnous Speed)
This parameter is mean motor rated speed,accroding to motor’s manufacturer
Set correct value。
z
Pr.203
Î
Full-Load SLIP-RPM
This parameter is mean slip rpm of motor,accroding to motor’s manufacturer
For example:if motor rated speed is 1720 rpm,please input 1800-1720=60 rpm
z
Pr.210
Î
Full Load Current(?% of AMP-Rating-Current)
Set the ratio of the motor’s rating to the driver’s rating.
Motor Full Load Current ratio (%) = (motor's full load current / driver's rating current) x100%。
z
Pr.211
Î
Filed Current(?% of Full-Load-Current)
Set the ratio of the motor’s exciting current to the motor’s full load current.
Motor Exciting Current Ratio (%) = (motor's exciting current / motor's full load current)x100%。
z
Pr.215
Î
Electronic Over-Load Thermal Relay Time
This Driver has built an electronic thermo function. If the driver volume is large then the motor
which is used, this function can prevent the motor overload. If this parameter sets to be 0, the
Electronic Thermo protect function is disabled.
Pr.215
150%
110%
(Irms /Pr.210)
TIME
z
Pr.216
Î
RESISTANCE(between V&W, U phase open)
z
Pr.217
Î
INDUCTANCE(between V&W, U phase open)
These two parameters should refer to the data of motor’s manufacturer, or can be auto
tuned by driver.