17.2.7 Alarm Mode of R-Panel【ALM Code Description】
ALARM CODE
DESCRIPTION and TROUBLESHOOTING
A0 - no
A0 – no
Î
No Error
No Error
A0 - PG
A0 – PG
Î
PG Error
Motor encoder signal feedback error
A0 - CF
A0 – CF
Î
Fan Error
Fan speed too slow or stopped
A0 – SE
A0 – SE
Î
Memory Error
EEPROM memory error
A0 – ES
A0 – ES
Î
Emergency Stop
Drive received emergency stop command form digital input or communication.
A0 – OD
A0 – Od
Î
Discharge Overtime
Drive electrical discharge time over protection time.
A0 - OL
A0 – OL
Î
Over Load
Drive over load time over protection time
A0 - OH
A0 – OH
Î
Over Heat
Temperature of heat sink over heat
A0 - OP
A0 – OP
Î
Over Power
Voltage over capacitance too high.
A0 - UP
A0 – UP
Î
Low Power
Voltage over capacitance too low, please check the power source.
A0 - OC
A0 – OC
Î
Over Current
Current output over protection level
A0 – Er.
A0 – Er.
Î
Communication Fail
Communication between panel and drive failed
17.2.8【Definition of Cables】
JAM SC-5P Connector:
Gap
Pin1
Pin5
PIN1
5V
PIN2
0V
PIN3
485-A
PIN4
485-B
PIN5
X(NC)
www.jps.com.tw