www.jps.com.tw
42
z
Pr.371
Î
AM1 Full Scale Data Range
This parameter sets the maximum full scale of the external analog meter. Note the rules listed
below:
1.
When execute the adjustment of AM1 signal, the output full scale is 100.0%; therefore, this
parameter should set to be 1000 for the need.
2.
After finishing the adjustment of AM1 signal, the output full scale should refer to the actual
external analog meter.
3.
AM1 output rating is 1V/1mA.
Example:
Frequency Meter (full scale 60.00Hz)
Î
the full scale should set to be 6000.
Current Meter (full scale 20.0A)
Î
the full scale should set to be 200.
Voltage Meter (full scale 500V)
Î
the full scale should set to be 500.
Speed Meter (full scale 1800rpm)
Î
the full scale should set to be 1800.
z
Pr.372
Î
AM1 Output Volume Setting
IF Pr.370 select function 15, the output of AM1 is set by this parameter. The range of this
parameter is 0.0% ~ 100.0%.
z
Pr.373
Î
AM1 100% Full Scale Adjustment
Be used for AM1 100% output scale adjustment.
z
Pr.374
Î
AM1 75% Scale Adjustment
Be used for AM1 75% output scale adjustment.
z
Pr.375
Î
AM1 50% Scale Adjustment
Be used for AM1 50% output scale adjustment.
z
Pr.376
Î
AM1 25% Scale Adjustment
Be used for AM1 25% output scale adjustment.
z
Pr.377
Î
AM1 12.5% Scale Adjustment
Be used for AM1 12.5% output scale adjustment.
Содержание IRIS-IMSV
Страница 1: ...IRIS IMSV DRIVER USER MANUAL Version V5 03 ...
Страница 95: ...16 CE Certificate 16 1 EMC Certificate www jps com tw 94 ...