198
JOHNSON CONTROLS
5276178-JIM-C-0118
User Interface Control Center
TABLE 90
-
BACNET MS/TP, MODBUS, BACNET IP (CONT'D)
(See notes at end of table)
BACnet NAME
USER
INTERFACE
NAME
READ/
WRITE
BACnet
OBJECT
TYPE AND
INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
MORN_WUP_CMD
MORNING WARM
UP CMND
R/W
AV86
1111
A BAS GENERATED COMMAND TO ALLOW THE
MORNING WARM UP FEATURE TO BE TURNED ON
AND OFF (0 = OFF / 1 = ON)
MORN_WUP_RAT
RAT HEATING
SETP
R/W
AV15
1040
ON A VAV OR FLEXSYS UNIT THIS IS THE
RETURN AIR TEMPERATURE SET POINT USED TO
DETERMINE WHEN THE UNIT SHOULD SWITCH TO
THE HEATING MODE (F)
NIGHT_SETBAC
NIGHT SET BACK
(FOR HEATING)
R/W
AV87
1112
THIS COMMAND ALLOWS THE NIGHT SET BACK
HEATING FUNCTION TO BE TURNED ON AND OFF
(0 = OFF / 1 = ON)
OA_DAMP_POS1
OA DAMPER MIN
POSITION 1
R/W
AV16
1041
THE MINIMUM POSITION FOR THE OUTDOOR
AIR DAMPER WHEN USING FIXED VENTILATION
CONTROL WHEN THE SUPPLY FAN IS AT FULL
SPEED (%)
OA_DAMP_POS2
OA DAMPER MIN
POSITION 2
R/W
AV17
1042
THE MINIMUM POSITION FOR THE OUTDOOR
AIR DAMPER WHEN USING FIXED VENTILATION
CONTROL WHEN THE SUPPLY FAN IS AT 50% OF
FULL SPEED (%)
OA_DAMPER
OA DAMPER
R
AI25
538
THIS IS THE POSITION OF THE OUTDOOR DAMPER
(%)
OA_ENTH_LIMT
OUTSIDE AIR
ENTHALPY
SETPOINT
R/W
AV18
1043
THE UPPER ENTHALPY LIMIT TO ALLOW THE
USE OF OUTDOOR AIR FOR SINGLE OR DUAL
ENTHALPY ECONOMIZER (BTU/LB)
OA_ENTHALPY
OUTSIDE AIR
ENTHALPY
R
AI26
539
ACTUAL OUTSIDE AIR ENTHALPY (BTU/LB)
OA_FLO_PRS_1
OA FLOW
PRESSURE 1
R
AI27
540
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
OA_FLO_PRS_2
OA FLOW
PRESSURE 2
R
AI28
541
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
OA_FLOW_1
IAQ DMPR AIR
FLOWS OA FLOW 1
R
A161
574
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
OA_FLOW_2
IAQ DMPR AIR
FLOWS OA FLOW 2
R
A162
575
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
OA_FLOW_TOTAL
OUTSIDE AIR
TOTAL FLOW
R
A163
576
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
OA_REL_HUMID
OUTSIDE AIR
HUMIDITY
R
AI29
542
ACTUAL OUTDOOR AIR RELATIVE HUMIDITY (%)
OA_TEMP
OUTSIDE AIR
TEMP
R
AI30
543
ACTUAL OUTDOOR AIR TEMPERATURE (F)
OAT_HIGH_SAT
OAT FOR HIGH SAT
R/W
AV19
1044
THE OUTDOOR TEMPERATURE THE CONTROL
USES WHEN USING OUTDOOR AIR SAT RESET TO
SWITCH TO THE SAT HIGH LIMIT SET POINT (F)
OAT_LOW_SAT
OAT FOR LOW SAT
R/W
AV20
1045
THE OUTDOOR TEMPERATURE THE CONTROL
USES WHEN USING OUTDOOR AIR SAT RESET TO
SWITCH TO THE SAT LOW LIMIT SET POINT (F)
OCC_MODE
OCCUPANCY
MODE
R
BI35
1316
IDENTIFIES THE OCCUPIED / UNOCCUPIED
STATUS WITH HARD WIRED, COMMUNICATED
OR INTERNAL CLOCK SCHEDULE INPUT
(ENA - ENABLED-OCCUPIED; DIS - DISABLED -
UNOCCUPIED)
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...