182
JOHNSON CONTROLS
5276178-JIM-C-0118
User Interface Control Center
TABLE 89 – SERVICE MODE (CONT'D)
DISPLAY TEXT
TYPE
ID
VALUE
RANGE
LOCATION
DESCRIPTION
VAV HEAT RELAY
DIGITAL
OUTPUT
TB1-12
ON / OFF
I/O BOARD
STATUS OF THE DIGITAL OUTPUT FOR THE
VAV HEAT RELAY
FAN FAULT
DIGITAL
OUTPUT
TB1-6
OKAY / FAULTED
I/O BOARD
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
COOL/HEATING
FAULT
DIGITAL
OUTPUT
TB1-8
ON / OFF
I/O BOARD
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
SENSOR/MISC
FAULT
DIGITAL
OUTPUT
TB1-10
ON / OFF
I/O BOARD
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
SUPPLY FAN VFD
SPEED
ANALOG
OUTPUT
TB9-1
0-10VDC
I/O BOARD
ANALOG OUTPUT TO THE SUPPLY FAN
VFD
EXHAUST
DAMPER
POSITION
ANALOG
OUTPUT
TB9-7
0-10VDC
I/O BOARD
ANALOG OUTPUT TO THE EXHAUST
DAMPER
EXHAUST /
RETURN FAN VFD
ANALOG
OUTPUT
TB9-3
0-10VDC
I/O BOARD
ANALOG OUTPUT TO THE EXHAUST OR
RETURN FAN VFD
OA DAMPER
POSITION
ANALOG
OUTPUT
TB9-5
0-10VDC
I/O BOARD
ANALOG OUTPUT TO THE ECONOMIZER
DAMPERS
HEATING VALVE
ANALOG
OUTPUT
TB9-9
0-10VDC
I/O BOARD
ANALOG OUTPUT TO THE HEATING VALVE
BYPASS DAMPER
POSITION
ANALOG
OUTPUT
TB9-11
0-10VDC
I/O BOARD
ANALOG OUTPUT TO THE FLEXSYS
BYPASS DAMPER
SUPPLY AIR TEMP
CURRENT
ANALOG
INPUT
J1-1
0-5 VOLTS
I/O BOARD
ANALOG INPUT FROM THE SUPPLY OR
MIXED AIR SENSOR
MX SUPPLY AIR
TEMP CURRENT
ANALOG
INPUT
J1-1
0-5 VOLTS
I/O BOARD
ANALOG INPUT FROM THE SUPPLY OR
MIXED AIR SENSOR
HEAT EXCHANGER
TEMP
ANALOG
INPUT
J1-2
0-5 VOLTS
I/O BOARD
ANALOG INPUT FROM THE TEMPERATURE
SENSOR POSITIONED BEFORE THE HEAT
SECTION
FLEX EVAP TEMP
CURRENT
ANALOG
INPUT
J1-3
0-5 VOLTS
I/O BOARD
ANALOG INPUT FROM THE TEMPERATURE
SENSORS POSITIONED ON THE LEAVING
SIDE OF THE EVAPORATOR COIL
OUTSIDE AIR
TEMP
ANALOG
INPUT
J2-1
0-5 VOLTS
I/O BOARD
ANALOG INPUT FROM THE OUTDOOR AIR
TEMPERATURE SENSOR
RETURN AIR TEMP
CURRENT
ANALOG
INPUT
J2-2
0-5 VOLTS
I/O BOARD
ANALOG INPUT FROM THE RETURN AIR
TEMPERATURE SENSOR
OUTSIDE AIR
HUMIDITY
ANALOG
INPUT
J2-3
0-5 VOLTS
I/O BOARD
ANALOG INPUT FROM THE OUTDOOR AIR
HUMIDITY SENSOR
RETURN AIR
HUMIDITY
ANALOG
INPUT
J2-4
0-5 VOLTS
I/O BOARD
ANALOG INPUT FROM THE RETURN AIR
HUMIDITY SENSOR
TEMPERATURE
SUCTION 1
ANALOG
INPUT
J3-1
0-5 VOLTS
I/O BOARD
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
TEMPERATURE
SUCTION 2
ANALOG
INPUT
J3-2
0-5 VOLTS
I/O BOARD
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...