TABLE 101 - WARNING DESCRIPTION
HISTORY
SCREEN
WORDING
DESCRIPTION
RESET
SHOW WHEN
UNIT TYPE IS
STATUS
SCREEN
WORDING
FAULT
OUTPUT
TYPE
WRN-
BUILDING
PRS
BUILDING STATIC PRES> 0.45 INWC OR < -0.45
INWC FOR 10 SECONDS. POWER EXHAUST
REVERTS TO NONE OR ON/OFF
AUTO RESET
POWER EXHAUST
OTHER THAN
NONE OR ON - OFF
DAMPER
EXHAUST
SYS STATUS
WARNING
SENSOR/
MISC FAULT
WRN-CO
2
SENSOR 1
OUTSIDE
OUTSIDE CO
2
SENSOR OUT OF RANGE FOR
MORE THAN OR EQUAL TO 15 MINUTES
AUTO RESET
VENTILATION
CONTROL EQUALS
DEMAND
VENTILATION
SYS STATUS
WARNING
SENSOR/
MISC FAULT
WRN-CO
2
SENSOR 2
INSIDE
OUTSIDE CO
2
SENSOR OUT OF RANGE FOR
MORE THAN OR EQUAL TO 15 MINUTES
AUTO RESET
VENTILATION
CONTROL EQUALS
DEMAND
VENTILATION
SYS STATUS
WARNING
SENSOR/
MISC FAULT
WRN-COMPR
SYSTEM *
INHIBIT
SEE DESCRIPTION AT THE END OF
THIS TABLE
AUTO RESET
COOLING
HEATING
FAULT
WRN-DIRTY
FILTER 1
THE FILTER STATUS INPUT IS CLOSED FOR
MORE THAN OR EQUAL TO 1 MINUTE
AUTO RESET
DIRTY FILTER
SWITCH IS
INSTALLED
FILTER STATUS
CHANGE
SENSOR/
MISC FAULT
WRN-DUCT
PRS XDCR
SUPPLY FAN OUTPUT ON, SUPPLY FAN STATUS
MUST BE RUNNING FOR 5 MINUTES, STATIC
PRESS CURRENT LESS THAN OR EQUAL
TO(0.333 X DUCT STATIC PRESS ACTIVE SP)
FOR 30 SECONDS
AUTO RESET
UNIT TYPE IS VAV
OR FLEXSYS
SUPPLY
SYS STATUS
WARNING
FAN FAULT
WRN-
EXHAUST
FAN
THE EXHAUST FAN OUTPUT IS ON FOR 45
SECONDS AND THE RUN VERIFICATION INPUT
IS LOW (OPEN) FOR 10 SECONDS
AUTO RESET
POWER EXHAUST
OTHER THEN NONE
EXHAUST
SYSTEM STATUS
WARNING
SENSOR/
MISC FAULT
WRN-
FREEZESTAT
TRIP
THE HW/STEAM FREEZSTAT CIRCUIT GOES
HIGH (CLOSED) BUT GOES LOW (OPEN) WITHIN
5 MINUTES
AUTO RESET
HEATING SYSTEM
TYPE EQUALS HOT
WATER STEAM
SENSOR/
MISC STATUS
WARNING
COOLING
HEATING
FAULT
WRN-
FURNACE
MULTIPLEXER
FAULT
ON MODULATING GAS THE HEAT BINARY
OUTPUTS DO NOT MATCH THE GAS FURANCE
STATUS INPUT.
SEE TABE 8-9 OR NO
FURNACE STATUS INPUT ON STAGED
GAS
AUTO RESET
HEATING SYSTEM
TYPE EQUALS
MODULATING GAS
OR STAGED GAS
SENSOR/
MISC STATUS
WARNING
COOLING
HEATING
FAULT
WRN-GAS
FURNACE
THE HEAT BINARY OUTPUTS DO NOT MATCH
THE GAS FURANCE STATUS INPUT.
SEE TABE
8-10
AUTO RESET
HEATING SYSTEM
TYPE EQUALS
STAGED GAS
COOLING
HEATING
FAULT
WRN-HET
SENSOR
THE HEAT ENTERING SENSOR IS OUT OF
RANGE FOR MORE THAN OR EQUAL TO 10
SECONDS
AUTO RESET
HEATING SYSTEM
TYPE IS STAGED
GAS OR ELECTRIC
SENSOR/
MISC STATUS
WARNING
SENSOR/
MISC FAULT
WRN-LOW
AMBIENT
TEMP *
THE OUTDOOR TEMP IS LESS THAN OR EQUAL
TO THE MECH COOL LOCKOUT TEMP
AUTO RESET
LOW AMBIENT PKG
IS NOT INSTALLED
FOR THE SYSTEM
COMP SYS *
STATUS LOW
AMB INHIBIT
SENSOR/
MISC FAULT
WRN-
OUTSIDE AIR
RH
OUTSIDE AIR TEMP MORE THAN OR EQUAL TO
32 F FOR 10 SECONDS OUTDOOR AIR
HUMIDITY < 5% FOR 10 SECONDS
AUTO RESET
ECONO INSTALLED
SINGLE ENTHALPY
OR DUAL ENTHALPY
SENSOR/
MISC STATUS
WARNING
SENSOR/
MISC FAULT
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...