TABLE 92 - N2 POINTS LIST (CONT'D)
(See notes at end of table)
B A C N E T
NAME
USER
I N T E R F A C E
NAME
READ/
WRITE
BACNET
OBJECT
TYPE
AND
INSTANCE
ENG
UNITS
N2
ADDRESS
POINTS LIST DESCRIPTION
MORN_WUP_
RAT
RAT HEATING
SETP
R/W
AV15
DEG F
AO 14
ON A VAV OR FLEXSYS UNIT THIS IS THE
RETURN AIR TEMPERATURE SET POINT USED TO
DETERMINE WHEN THE UNIT SHOULD SWITCH TO
THE HEATING MODE (F)
NIGHT_
SETBAC
NIGHT SET BACK
(FOR HEATING)
R/W
AV87
0, 1
AO 38
THIS COMMAND ALLOWS THE NIGHT SET BACK
HEATING FUNCTION TO BE TURNED ON AND OFF
(0 = OFF / 1 = ON)
OA_DAMPER
OA DAMPER
R
AI25
%
AI 18
THIS IS THE POSITION OF THE OUTDOOR
DAMPER (%)
OA_DAMP_
POS1
OA DAMPER MIN
POSITION 1
R/W
AV16
%
AO 15
THE MINIMUM POSITION FOR THE OUTDOOR
AIR DAMPER WHEN USING FIXED VENTILATION
CONTROL WHEN THE SUPPLY FAN IS AT FULL
SPEED (%)
OA_DAMP_
POS2
OA DAMPER MIN
POSITION 2
R/W
AV17
%
AO 16
THE MINIMUM POSITION FOR THE OUTDOOR
AIR DAMPER WHEN USING FIXED VENTILATION
CONTROL WHEN THE SUPPLY FAN IS AT 50% OF
FULL SPEED (%)
OA_ENTHALPY
OUTSIDE AIR
ENTHALPY
R
AI26
BTU/LB
AI 19
ACTUAL OUTSIDE AIR ENTHALPY (BTU/LB)
OA_ENTH_
LIMT
OUTSIDE AIR
ENTHALPY
SETPOINT
R/W
AV18
BTU/LB
AO 17
THE UPPER ENTHALPY LIMIT TO ALLOW THE
USE OF OUTDOOR AIR FOR SINGLE OR DUAL
ENTHALPY ECONOMIZER (BTU/LB)
OA_FLO_
PRS_1
OA FLOW
PRESSURE 1
R
AI27
WC
AI 20
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
OA_FLO_
PRS_2
OA FLOW
PRESSURE 2
R
AI28
WC
AI 21
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
OA_REL_
HUMID
OUTSIDE AIR
HUMIDITY
R
AI29
%
AI 22
ACTUAL OUTDOOR AIR RELATIVE HUMIDITY (%)
OA_TEMP
OUTSIDE AIR
TEMP
R
AI30
DEG F
AI 23
ACTUAL OUTDOOR AIR TEMPERATURE (F)
OCCUPNCY_
CMD
OCCUPANCY
COMMAND
R/W
AV88
0, 1
AO 39
THIS BAS COMMAND ALLOWS THE UNIT TO BE
PLACED IN THE OCCUPIED OR UNOCCUPIED
MODE (0 = UNOCCUPIED / 1 = OCCUPIED)
OCC_ZN_
COOL
OCCUPIED ZONE
COOLING SETP
R/W
AV21
DEG F
AO 18
THE OCCUPIED ZONE COOLING SET POINT (F)
OCC_ZN_HEAT
OCCUPIED ZONE
HEATING SETP
R/W
AV22
DEG F
AO 19
THE OCCUPIED ZONE HEATING SET POINT (F)
PRS_1_DISCH
PRESSURES 1
DISCHARGE
R
AI31
PSI
AI 24
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
PRS_1_
SUCTION
PRESSURES 1
SUCTION
R
AI32
PSI
AI 25
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...