127
JOHNSON CONTROLS
5276178-JIM-C-0118
5
Staged Input
The unit requires the following digital inputs in order
to operate in the
“STAGED”
mode of operation. The
inputs are made at the low voltage terminal block of
the unit.
•
W1 LOW HEAT - Terminal 12 of CTB3
•
W2 HIGH HEAT - Terminal 13 of CTB3
•
Y1 LOW COOL - Terminal 10 of CTB3
•
Y2 HIGH COOL - Terminal 11 of CTB3
Table 59 shows what the Unit Mode would be, based
on the digital inputs.
Zone Temperature Control
Hardwired Or Communicated
The unit compares the analog
“WIRED ZONE TEMP”
or
“COMM ZONE TEMP”
input to the
“OCC ZONE
COOLING”, “OCC ZONE HEATING” ,”UNOCC
ZONE COOLING”,
or
“UNOCC ZONE HEATING”
set points to determine the sub-mode of operation. The
following parameters must be programmed through the
User Interface:
•
“OCC ZONE COOLING SETPOINT” –
SETPOINTS key / COOLING subsection
•
“UNOCC ZONE COOLING SETPOINT” –
SETPOINTS key / COOLING subsection
•
“OCC ZONE HEATING SETPOINT” –
SETPOINTS key / HEATING subsection
•
“UNOCC ZONE HEATING SETPOINT”
–
SETPOINTS key / HEATING subsection
Y1
LOW
COOL
Y2
HIGH
COOL
W1
LOW
HEAT
W2
HIGH
HEAT
CURRENT
OPER MODE
UNIT MODE
ON
OFF
OFF
OFF
OCCUPIED
OCCUPIED COOLING LOW
ON/OFF
ON
OFF
OFF
OCCUPIED
OCCUPIED COOLING HIGH
OFF
OFF
ON
OFF
OCCUPIED
OCCUPIED HEATING LOW
OFF
OFF
ON/OFF
ON
OCCUPIED
OCCUPIED HEATING HIGH
OFF
OFF
OFF
OFF
OCCUPIED
OCCUPIED STANDBY
(SEE ALSO COMFORT VENTILATION OPERATION)
ON
OFF
OFF
OFF
UNOCCUPIED
UNOCCUPIED COOLING LOW
ON/OFF
ON
OFF
OFF
UNOCCUPIED
UNOCCUPIED COOLING HIGH
OFF
OFF
ON
OFF
UNOCCUPIED
UNOCCUPIED HEATING LOW
OFF
OFF
ON/OFF
ON
UNOCCUPIED
UNOCCUPIED HEATING HIGH
OFF
OFF
OFF
OFF
UNOCCUPIED
UNOCCUPIED STANDBY
TABLE 68 - DIGITAL INPUTS FOR STAGED INPUT STAGED INPUT MODE
FIGURE 65 - DIFFERENCES (°F) BETWEEN ZONE TEMPERATURE AND SET POINTS
COOLING LOW
COOLING HIGH
-2.0
1.5
-1.0
-0.5
+0.5
+1.0
+1.5
+2.0
Difference Between "ZONE TEMP" and "OCC ZONE COOLING"
or "UNOCC ZONE COOLING" Set Point
OFF
ON
OFF
ON
HEATING LOW
HEATING HIGH
Difference Between "ZONE TEMP" and "OCC ZONE HEATING"
or "UNOCC ZONE HEATING" Set Point
OFF
ON
OFF
ON
S
E
T
P
O
I
N
T
LD010572
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...