197
JOHNSON CONTROLS
5276178-JIM-C-0118
6
TABLE 90
-
BACNET MS/TP, MODBUS, BACNET IP (CONT'D)
(See notes at end of table)
BACnet NAME
USER
INTERFACE
NAME
READ/
WRITE
BACnet
OBJECT
TYPE AND
INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
FURN_OUT_4
ELECTRIC HEAT
STAGE 4 STG GAS
FURNACE 2 HIGH
R
BI29
1310
INDICATES THE STATUS OF THE BINARY OUTPUT
TO THE INDICATED HEAT SECTION (OFF - 0, ON - 1)
FURN_OUT_5
ELECTRIC HEAT
STAGE 5 STG GAS
FURNACE 3 LOW
R
BI30
1311
INDICATES THE STATUS OF THE BINARY OUTPUT
TO THE INDICATED HEAT SECTION (OFF - 0, ON - 1)
FURN_OUT_6
ELECTRIC HEAT
STAGE 6 STG GAS
FURNACE 3 HIGH
R
BI31
1312
INDICATES THE STATUS OF THE BINARY OUTPUT
TO THE INDICATED HEAT SECTION (OFF - 0, ON - 1)
FURN_OUT_7
ELECTRIC HEAT
STAGE 7
R
BI32
1313
INDICATES THE STATUS OF THE BINARY OUTPUT
TO THE INDICATED HEAT SECTION (OFF - 0, ON - 1)
HEAT_ENABLE
HEATING ENABLE
R/W
AV(BV)83
1108
A COMMUNICATED INPUT THAT ALLOWS THE
HEATING FUNCTION TO BE TURNED ON AND OFF
(0 = ENABLED; 1 = DISABLED)
HEAT_ENT_TMP
HEAT ENTERING
TEMP
R
AI22
535
ACTUAL TEMPERATURE OF THE AIR ENTERING
THE STAGED HEAT SECTION (F)
HEAT_STAGES
ELECTRIC HEAT
STAGES GAS HEAT
STAGES
R
AI23
536
DERIVED VALUE SHOWING THE NUMBER OF
ELECTRIC OR STAGED GAS HEAT STAGES
AVAILABLE (1 - 7)
HEAT_VACTION
HEATING VALVE
ACTION
R/W
AV(BV)84
1109
A COMMUNICATED INPUT THAT ALLOWS THE
HEATING VALVE ACTION TO BE CHANGED (0 =
DIRECTI ACTING; 1 = REVERSE ACTING)
HEATING_SAT
HEATING SAT
R/W
AV09
1034
THE HEATING SAT SET POINT FOR A VAV OR
FLEXSYS UNIT (F)
HEATING_VALV
HEATING VALVE
R
AI24
537
THE OUTPUT FROM THE CONTROL TO A HOT
WATER, STEAM, OR MODULATING GAS HEAT
VALVE (%)
HW_FRZ_STAT
HOT WATER FRZ
STATUS
R
BI33
1314
THE STATUS OF THE FREEZESTAT CIRCUIT ON
UNITS WITH HOT WATER OR STEAM HEAT. (0 - NO
FAULT / 1 = FAULTED)
LOCAL_STOP
LOCAL STOP
R
BI34
1315
IDENTIFIES THE STATUS OF THE HARDWIRED
BINARY INPUT OF THE LOCAL STOP (RUN / STP -
STOP)
MAX_BYPASS
MAXIMUM BYPASS
R/W
AV10
1035
THE MAXIMUM ALLOWABLE SETTING FOR THE BY
PASS DAMPER IN A FLEXSYS UNIT (%)
MAX_FLOW_DV
MAX FLOW
DEMAND
VENTILATION
R/W
AV11
1036
THIS FEATURE IS NOT AVAIL-
ABLE ON THIS UNIT.
MECH_LCK_TMP
MECH CLG
LOCKOUT TEMP
R/W
AV12
1037
THE MINIMUM OUTDOOR TEMPERATURE AT
WHICH MECHANICAL COOLING IS ALLOWED TO
OPERATE (F)
MIN_FLOW_DV
MIN FLOW
DEMAND
VENTILATION
R/W
AV13
1038
THIS FEATURE IS NOT AVAIL-
ABLE ON THIS UNIT.
MIXD_SAT_LIM
MIXED SAT LIMIT
R/W
AV14
1039
ON A FLEXSYS UNIT THIS IS THE SUPPLY AIR
SETPOINT WHEN OPERATING WITHOUT A BYPASS
DAMPER (F)
MORN_WARM_UP
MORNING WARM
UP ENABLE
R/W
AV(BV)85
1110
A COMMUNICATED INPUT THAT ALLOWS MORNING
WARM UP TO BE TURNED ON AND OFF (0 =
ENALBED; 1 = DISABLED)
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...