User Interface Control Center
TABLE 84 - HEATING
DISPLAY TEXT
PASS
WORD
LEVEL
RANGE
DEFAULT SETTING LOCATION
SHOW WHEN UNIT TYPE
IS
HEATING SYS STATUS
NORMAL - ACTIVE /
NORMAL - INACTIVE
/ FAULTED / USER
DISABLED / UNDER
FLOOR CONTROL /
NONE
DERIVED
ALWAYS
HEATING SYSTEM
TYPE
2
NONE / ELECTRIC/
STAGED GAS/
MODULATING GAS/
HOT WATER/ STEAM
NONE
OPTIONS / HEATING
ALWAYS
GAS HEAT CAPACITY
2
375 MBH / 750 MBH /
1125 MBH
375 MBH
OPTIONS / HEATING
HEAT TYPE EQUALS STAGED
GAS OR MODULATING GAS
ELEC HEAT CAPACITY
2
40 KW - 200V
40 KW
40 KW
OPTIONS / HEATING
HEAT TYPE EQUALS
ELECTRIC
SUPPLY AIR TEMP
CURRENT
-20.0º F TO 180.0º F
LOOK UP
TABLE
HEAT TYPE DOES NOT EQUAL
NONE
ACTIVE SP
50.0º F TO 120.0º F
DERIVED
ZONE TEMP*
CURRENT
-20.0º F TO 180.0º F
LOOK UP
TABLE
ALWAYS
OCC ZONE HEATING
SETPOINT
1
60º F TO OCC ZONE
COOLING SETPOINT
-2.0
°F
68º F
SETPOINTS / HEATING
ZONE TEMP*
CURRENT
-20.0
°F
TO 180.0
°F
LOOK UP
TABLE
ALWAYS
UNOCC ZONE
HEATING
SETPOINT
1
50º F TO UNOCC ZONE
COOLING SETPOINT
-2.0
°F
60.0º F
SETPOINTS / HEATING
RETURN AIR TEMP
CURRENT
-20.0º F TO 180.0º F
LOOK UP
TABLE
HEAT TYPE DOES NOT EQUAL
NONE AND UNIT EQUALS
VARIABLE AIR VOLUM OR
FLEXSYS
RAT HEATING
SETPOINT
1
55.0º F - RAT COOLING
SETPOINT -2.0º F
68.0º F
SETPOINTS / HEATING
HEAT ENTERING TEMP
-20.0º F TO 180.0º F
LOOK UP
TABLE
HEAT TYPE EQUALS STAGED
GAS
STAGED HEAT STATUS
STGS ON
0 TO 6
DERIVED
HEAT TYPE EQUALS
ELECTRIC OR STAGED GAS
STGS AVAL
2 TO 6
DERIVED
HW / STEAM
VALVE POS
0.0 TO 100%
DERIVED
HEAT TYPE EQUALS HOT
WATER HEAT STEAM
FRZ STAT
OK TRIPPED
DERIVED
* ONLY THE ZONE TEMP SCREEN FOR THE CURRENT ACTIVE MODE WILL BE SHOWN.
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...