185
JOHNSON CONTROLS
5276178-JIM-C-0118
6
TABLE 89 – SERVICE MODE (CONT'D)
DISPLAY TEXT
TYPE
ID
VALUE
RANGE
LOCATION
DESCRIPTION
SAFETY INPUTS
LPCO 1
D I G I TA L
INPUT
TB7-5
OKAY / FAULTED
I/O BOARD
THE LOW PRESSURE CUTOUT IS
CONTAINED IN THE SAFETY INPUT CHAIN
1 CIRCUIT
SAFETY INPUTS
LPCO 2
D I G I TA L
INPUT
TB7-7
OKAY / FAULTED
I/O BOARD
THE LOW PRESSURE CUTOUT IS
CONTAINED IN THE SAFETY INPUT CHAIN
2 CIRCUIT
SAFETY INPUTS
LPCO 3
D I G I TA L
INPUT
TB7-8
OKAY / FAULTED
I/O BOARD
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
SUPPLY FAN
OUTPUT
DIGITAL
INPUT
TB7-10
RUNNING /
STOPPED
I/O BOARD
DIGITAL INPUT FOR THE SUPPLY FAN
RUN VERIFICATION CIRCUIT
EXHAUST FAN
STATUS
DIGITAL
INPUT
TB7-11
RUNNING /
STOPPED
I/O BOARD
DIGITAL INPUT FROM THE EXHAUST FAN
RUN VERIFICATION CIRCUIT
RETURN FAN
STATUS
DIGITAL
INPUT
TB7-11
RUNNING /
STOPPED
I/O BOARD
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
FILTER STATUS
DIGITAL
INPUT
TB7-13
OKAY / CHANGE
I/O BOARD
DIGITAL INPUT FROM THE DIRTY FILTER
PRESSURE SWITCH
HW/STEAM
FRZ STAT
DIGITAL
INPUT
TB7-14
OKAY / FAULTED
I/O BOARD
DIGITAL INPUT FROM THE HOT WATER
FREEZESTAT
SMOKE PURGE 1
DIGITAL
INPUT
TB8-4
ON / OFF
I/O BOARD
HARDWIRED DIGITAL INPUT TO PLACE
THE UNIT IS SMOKE PURGE 1 MODE
SMOKE PURGE 2
DIGITAL
INPUT
TB8-5
ON / OFF
I/O BOARD
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
SMOKE PURGE 3
DIGITAL
INPUT
TB8-7
ON / OFF
I/O BOARD
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
CO
2
LVL INSIDE
BAS
COMMUN
PORT
P1
USER DISABLE /
USER ENABLE
IPU BOARD
THIS ITEM MUST BE ENABLED IN ORDER
TO COMMUNICATE A CO
2
VALUE TO THE
UNIT
CO
2
LVL INSIDE
VALUE BAS
COMMUN
PORT
P1
101 TO 1899 PPM
IPU BOARD
THE INSIDE C02 VALUE BEING
COMMUNICATED TO THE UNIT
THROUGH THE BAS SYSTEM
DUCT PRES
RESET BAS
COMMUN
PORT
P1
USER DISABLE /
USER ENABLE
IPU BOARD
THIS ITEM MUST BE ENABLED IN ORDER
TO COMMUNICATE A DUCT STATIC
PRESSURE RESET VALUE TO THE UNIT
DUCT STATIC
PRES RESET BAS
COMMUN
PORT
P1
0 TO 100%
IPU BOARD
THE DUCT STATIC RESET VALUE
BEING COMMUNICATED TO THE UNIT
THROUGH THE BAS SYSTEM
FAN (G) BAS
COMMUN
PORT
P1
ON / OFF
IPU BOARD
GIVES THE STATUS OF THE
COMMUNICATED FAN G INPUT
MORNING WARM
UP CMD
COMMUN
PORT
P1
ON / OFF
IPU BOARD
GIVES THE STATUS OF THE
COMMUNICATED MORNING WARM UP
COMMAND
OCCUPANCY
COMMAND
COMMUN
PORT
P1
OCCUPIED /
UNOCCUPIED
IPU BOARD
GIVES THE STATUS OF THE
COMMUNICATED OCCUPANCY
COMMAND
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...