JOHNSON CONTROLS
5276178-JIM-C-0118
User Interface Control Center
COMMUNICATION
The Unit Controller is designed to communicate with a
Building Automation System and a printer.
The Building Automation System communication uses
BACnet protocol, MS/TP, Modbus I/O, Modbus Server,
Modbus Client or Terminal. Other Building Automation
system networks can be connected by using a router.
The printer communication uses ASCII protocol and
RS-232 hardware.
Communication Ports
The IPU Control board has four serial communication
ports. BACnet MS/TP must use Port 1 and Terminal
must use Port 2, which is the RS232 Port. Other
protocols may be selected on Ports 3 or 4.
BACnet Wiring
All BACnet devices are “daisy chained” together using
a twisted pair, the (+) is connected to the (+) and the
(-) to the (-). Do not connect wiring to terminals 1, 2
or 5. The connections on the PORT 1 connector are as
follows:
1 - 5V
2 - Ground
3 - Receive (-)
4 - Transmit (+)
5 - Open
Device Object Instance (DE)
The unit is shipped to automatically establish the DE
address after the MAC address is established using the
MAC address switches on the IPU or through the User
Interface. The default Device Object Instance (DE)
would be 23000 plus the MAC address. For example,
If you had a MAC address of 10 the default Object
Instance (DE) would be 23010.
The MAC address can be set in two ways using the MAC
Address Switches on the IPU or though the SERVICE
key of the User Interface. The 8-way binary switch
uses seven of the rockers to set the MAC address.
The network address must be between 1 and 127. To
determine the node address, add the value of each DIP
switch in the ON position as shown in Figure 69. Switch
8 must always be in the ON position to allow terminal
operation.
1
2
3
4
5
6
7
8
1
0
4
0
16
21
0
0
MAC Address 21
MAC Address 99
1
2
3
4
5
6
7
8
1
2
0
0
0
99
32
64
FIGURE 69 - MAC ADDRESS SWITCHES
LD10821
FIGURE 73 - IPU CONTROL BOARD
LD11197B
PORT 1 (J4)
PORT 4 (J3)
PORT 2 (J5)
PORT 3 (J2)
NOT USED
MAC ADDRESS SWITCH
SW2
SW1
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...