STEAM HEAT
The Johnson Controls Series 40 units (25, 30 and 40
Ton sizes) can be furnished with a Johnson Controls
single row steam coil. Johnson Controls steam coils are
a factory installed option.
The steam control valve, power and
control wiring to the actuator of the
valve are the responsibility of the in
-
stalling party.
All piping and control valves, and
wiring that is field installed must be
properly insulated and conform to all
local and national codes.
There are no provisions in the coil or
control sequence to prevent freezing of
condensate. The control valve, piping
and field installed wiring connections
are particularly vulnerable because
they are installed in the vestibule
outside of the conditioned air stream.
The installing party will be responsible
for properly insulating and installing
power and control wiring, to the actua
-
tor and piping.
DO NOT use steam coils as hot water
coils under any circumstances. In
steam coil systems, the steam pressure
shall not exceed 15 PSI.
FIGURE 30 – STEAM PIPING CROSS-SECTION
LD14190