TABLE 89 – SERVICE MODE (CONT'D)
DISPLAY TEXT
TYPE
ID
VALUE
RANGE
LOCATION
DESCRIPTION
SUPPLY AIR
TEMP RST
A N A L O G
INPUT
J7-4
0-5 VOLTS
I/O BOARD
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
DUCT STATIC
PRES RESET
A N A L O G
INPUT
J7-5
0-5 VOLTS
I/O BOARD
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
FURNACE STATUS
A N A L O G
INPUT
J5-1
0-5 VOLTS
I/O BOARD
ANALOG INPUT OF THE FURNACE
MULTIPLEXER
FURNACE 1A
STAT HI
D I G I TA L
INPUT
TB01-3
ON / OFF
FURNACE MULTIPLEXER
FURNACE 1A HZ STATUS INPUT TO
FURNACE MULTIPLEXER BOARD
FURNACE STATUS
COUNTS
A N A L O G
INPUT
J5-1
0 - 4095
I/O BOARD
STATUS OF THE INPUT FROM THE
FURNACE MULTIPLEXER BOARD IN
COUNT
FURNACE 1 STATUS
D I G I TA L
INPUT
TB01-2
ON / OFF
FURNACE MULTIPLEXER
FURNACE 1 STATUS INPUT TO FURNACE
MULTIPLEXER BOARD
FURNACE 1A STATUS
D I G I TA L
INPUT
TB01-2
ON / OFF
FURNACE MULTIPLEXER
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
FURNACE 1B STATUS
D I G I TA L
INPUT
TB01-6
ON / OFF
FURNACE MULTIPLEXER
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
FURNACE 2 STATUS
D I G I TA L
INPUT
TB01-3
ON / OFF
FURNACE MULTIPLEXER
FURNACE 2 STATUS INPUT TO FURNACE
MULTIPLEXER BOARD
FURNACE 3 STATUS
D I G I TA L
INPUT
TB01-4
ON / OFF
FURNACE MULTIPLEXER
FURNACE 3 STATUS INPUT TO FURNACE
MULTIPLEXER BOARD
O C C U P A N C Y
STATE
D I G I TA L
INPUT
TB8-2
OCCUPIED /
UNOCCUPIED
I/O BOARD
HARDWIRED DIGITAL INPUT TO PUT THE
UNIT INTO THE OCCUPIED MODE
LOCAL STOP
D I G I TA L
INPUT
TB8-1
RUN / STOP
I/O BOARD
DIGITAL INPUT THAT TURNS THE UNIT ON
AND OFF
FAN (G)
D I G I TA L
INPUT
TB8-8
ON / OFF
I/O BOARD
HARDWIRED DIGITAL INPUT TO TURN THE
SUPPLY FAN ON AND OFF
Y1 LOW COOL
D I G I TA L
INPUT
TB8-10
ON / OFF
I/O BOARD
HARDWIRED DIGITAL INPUT TO PLACE
THE UNIT IN FIRST STAGE COOLING MODE
Y2 HIGH COOL
D I G I TA L
INPUT
TB8-11
ON / OFF
I/O BOARD
HARDWIRED DIGITAL INPUT TO PLACE
THE UNIT IN SECOND STAGE COOLING
MODE
W1 LOW HEAT
D I G I TA L
INPUT
TB8-13
ON / OFF
I/O BOARD
HARDWIRED DIGITAL INPUT TO PLACE
THE UNIT IN FIRST STAGE HEATING MODE
W2 HIGH HEAT
D I G I TA L
INPUT
TB8-14
ON / OFF
I/O BOARD
HARDWIRED DIGITAL INPUT TO PLACE
THE UNIT IN SECOND STAGE HEATING
MODE
S A F E T Y I N P U T
CHAIN 1
D I G I TA L
INPUT
TB7-1
OKAY / FAULTED
I/O BOARD
DIGITAL INPUT FROM THE COMPRESSOR
SYSTEM 1 SAFETY CIRCUIT
S A F E T Y I N P U T
CHAIN 2
D I G I TA L
INPUT
TB7-2
OKAY / FAULTED
I/O BOARD
DIGITAL INPUT FROM THE COMPRESSOR
SYSTEM 2 SAFETY CIRCUIT
S A F E T Y I N P U T
CHAIN 3
D I G I TA L
INPUT
TB7-4
OKAY / FAULTED
I/O BOARD
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...