User Interface Control Center
TABLE 91
-
LON POINTS LIST (CONT'D)
(See notes at end of table)
BACnet NAME
USER
INTERFACE
NAME
BACnet
OBJECT
TYPE
AND IN-
STANCE
SNVT
POINTS LIST DESCRIPTION
nvoHW_FRZ_STAT
HOT WATER FRZ
STATUS
BI-033
SNVT_switch
(95)
THE STATUS OF THE FREEZESTAT CIRCUIT ON UNITS WITH
HOT WATER OR STEAM HEAT. (FLT - FAULTED / NFL - NO FAULT)
nviMAX_BYPASS
MAXIMUM BYPASS
AV-010
SNVT_switch
(95)
THE MAXIMUM ALLOWABLE SETTING FOR THE BY PASS
DAMPER IN A FLEXSYS UNIT (%)
nviMAX_FLOW_DV
MAX FLOW
DEMAND VENTILA-
TION
AV-011
SNVT_count_f
(51)
THIS FEATURE IS NOT AVAILABLE ON THIS PRODUCT.
nviMECH_LCK_TMP
MECH CLG LOCK-
OUT TEMP
AV-012
SNVT_count_f
(51)
THE MINIMUM OUTDOOR TEMEPRATURE AT WHICH MECHANI-
CAL COOLING IS ALLOWED TO OPERATE (F)
nviMIN_FLOW_DV
MIN FLOW
DEMAND VENTILA-
TION
AV-013
SNVT_count_f
(51)
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
nviMIXD_SAT_LIM
MIXED SAT LIMIT
AV-014
SNVT_count_f
(51)
ON A FLEXSYS UNIT THIS IS THE SUPPLY AIR SETPOINT WHEN
OPERATING WITHOUT A BYPASS DAMPER (F)
nviMORN_WUP_CMD
MORNING WARM
UP CMND
AV-086
SNVT_switch
(95)
A BAS GENERATED COMMAND TO ALLOW THE MORNING
WARM UP FEATURE TO BE TURNED ON AND OFF (0 = OFF / 1
= ON)
nviMORN_WUP_RAT
RAT HEATING
SETP
AV-015
SNVT_count_f
(51)
ON A VAV OR FLEXSYS UNIT THIS IS THE RETURN AIR TEM
-
PERATURE SET POINT USED TO DETERMINE WHEN THE UNIT
SHOULD SWITCH TO THE HEATING MODE (F)
nviNIGHT_SETBAC
NIGHT SET BACK
(FOR HEATING)
AV-077
SNVT_switch
(95)
THIS COMMAND ALLOWS THE NIGHT SET BACK HEATING FUC
-
TION TO BE TURNED ON AND OFF (0 = OFF / 1 = ON)
nvoOA_DAMPER
OA DAMPER
AI-025
SNVT_switch
(95)
THIS IS THE POSITION OF THE OUTDOOR DAMPER (%)
nviOA_DAMP_POS1
OA DAMPER MIN
POSITION 1
AV-016
SNVT_switch
(95)
THE MINIMUM POSITION FOR THE OUTDOOR AIR DAMPER
WHEN USING FIXED VENTILATION CONTROL WHEN THE SUP
-
PLY FAN IS AT FULL SPEED (%)
nviOA_DAMP_POS2
OA DAMPER MIN
POSITION 2
AV-017
SNVT_switch
(95)
THE MINIMUM POSITION FOR THE OUTDOOR AIR DAMPER
WHEN USING FIXED VENTILATION CONTROL WHEN THE SUP
-
PLY FAN IS AT 50% OF FULL SPEED (%)
nvoOA_ENTHALPY
OUTSIDE AIR
ENTHALPY
AI-026
SNVT_count_f
(51)
ACTUAL OUTSIDE AIR ENTHALPY (BTU/LB)
nviOA_ENTH_LIMT
OA ENTHALPY
LIMIT
AV-018
SNVT_count_f
(51)
THE UPPER ENTHALPY LIMIT TO ALLOW THE USE OF OUT
-
DOOR AIR FOR SINGLE OR DUAL ENTHALPY ECONOMIZER
(BTU/LB)
nvoOA_FLO_PRS_1
OA FLOW PRES
-
SURE 1
AI-027
SNVT_count_f
(51)
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
nvoOA_FLO_PRS_2
OA FLOW PRES
-
SURE 2
AI-028
SNVT_count_f
(51)
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
nvoOA_REL_HUMID
OUTSIDE AIR
HUMIDITY
AI-029
SNVT_switch
(95)
ACTUAL OUTDOOR AIR RELATIVE HUMIDITY (%)
nvoOA_TEMP
OUTSIDE AIR TEMP
AI-030
SNVT_count_f
(51)
ACTUAL OUTDOOR AIR TEMPERATURE (F)
nviOCCUPNCY_CMD
OCCUPANCY COM-
MAND
AV-088
SNVT_switch
(95)
THIS BAS COMMAND ALLOWS THE UNIT TO BE PLACED IN THE
OCCUPIED OR UNOCCUPIED MODE (0 = UNOCCUPIED / 1 =
OCCUPIED)
nviOCC_ZN_COOL
OCCUPIED ZONE
COOLING SETP
AV-021
SNVT_count_f
(51)
THE OCCUPIED ZONE COOLING SET POINT (F)
nviOCC_ZN_HEAT
OCCUPIED ZONE
HEATING SETP
AV-022
SNVT_count_f
(51)
THE OCCUPIED ZONE HEATING SET POINT (F)
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...