96
JOHNSON CONTROLS
5276178-JIM-C-0118
Start-up
TABLE 44 - 40 TON DRIVE ADJUSTMENT FOR CONSTANT VOLUME & VAV UNITS CLASS 1 & 2 FC FAN
10 HP MOTOR & 617 RPM DRIVE
15 HP MOTOR & 652 RPM DRIVE
20 HP MOTOR & 728 RPM DRIVE
25 HP MOTOR & 780 RPM DRIVE
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
91.8
4.5
42
88.2
4.5
44
82.5
4.7
46
83.7
5.1
50
95.9
4.7
44
92.1
4.7
46
86.0
4.9
48
86.9
5.3
52
100
(STD.)
4.9
1
46
96.0.0
4.9
48
89.5
5.1
50
90.2
5.5
54
104.1
5.1
48
100.0
(STD.)
5.1
1
50
93.0
5.3
52
93.4
5.7
56
108.2
5.3
50
103.9
5.3
52
96.5
5.5
54
96.7
5.9
58
112.2
5.5
52
107.8
5.5
54
100.0
(STD.)
5.7
1
56
100.0
(STD.)
6.1
1
60
116.3
5.7
54
111.7
5.7
56
103.5
5.9
58
103.3
6.3
62
-
-
-
115.6
5.9
58
107.0
6.1
60
106.6
6.5
64
-
-
-
119.5
6.1
60
110.5
6.3
62
109.8
6.7
66
-
-
-
123.4
6.3
62
114.0
6.5
64
113.1
6.9
68
-
-
-
127.4
6.5
64
117.5
6.7
66
116.4
7.1
70
-
-
-
-
-
66
121.1
6.9
68
119.7
7.5
74
TABLE 45 - DRIVE ADJUSTMENT FOR POWER EXHAUST - 25 TON
5 HP MOTOR & 758 RPM DRIVE
7.5 HP MOTOR & 852 RPM DRIVE
10 HP MOTOR & 976 RPM DRIVE
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D PD
BROWNING
2B5V_ _
100
4.9 (STD.)
1
46
92
5.1
48
93
5.9
56
104
5.1
48
96
5.3
50
97
6.1
58
109
5.3
50
100
5.5 (STD.)
1
52
100
6.3 (STD.)
1
60
113
5.5
52
104
5.7
54
103
6.5
62
117
5.7
54
108
5.9
56
107
6.7
64
122
5.9
56
112
6.1
58
110
6.9
66
TABLE 46 - DRIVE ADJUSTMENT FOR POWER EXHAUST - 30 & 40 TON
7.5 HP MOTOR & 852 RPM DRIVE
10 HP MOTOR & 976 RPM DRIVE
15 HP MOTOR & 1069 RPM DRIVE
% RPM
& CFM
REQ'D
PD (IN)
BROWNING
2B5V_ _
% RPM
& CFM
REQ'D
PD (IN)
BROWNING
2B5V_ _
% RPM
& CFM
REQ'D
PD (IN)
BROWNING
2B5V_ _
96.4
5.3
52
93.7
5.9
58
94.2
6.5
64
100.0
(STD.) 5.5
1
54
96.8
6.1
60
97.1
6.7
66
103.6
5.7
56
100
(STD.) 6.3
1
62
100.0
(STD.) 6.9
1
68
107.3
5.9
58
103.2
6.5
64
102.9
7.1
70
110.9
6.1
60
106.3
6.7
66
108.7
7.5
74
114.5
6.3
62
109.5
6.9
68
117.4
8.1
80
1. (STD), STANDARD FACTORY SUPPLIED DRIVE. ALL OTHER DRIVE COMBINATIONS MUST BE PURCHASED AND FIELD INSTALLED.
1. (STD), STANDARD FACTORY SUPPLIED DRIVE. ALL OTHER DRIVE COMBINATIONS MUST BE PURCHASED AND FIELD INSTALLED.
1. (STD), STANDARD FACTORY SUPPLIED DRIVE. ALL OTHER DRIVE COMBINATIONS MUST BE PURCHASED AND FIELD INSTALLED.
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...