207
JOHNSON CONTROLS
5276178-JIM-C-0118
6
TABLE 91
-
LON POINTS LIST (CONT'D)
(See notes at end of table)
BACnet NAME
USER
INTERFACE
NAME
BACnet
OBJECT
TYPE
AND IN-
STANCE
SNVT
POINTS LIST DESCRIPTION
nvoPRS_1_DISCH
PRESSURES 1
DISCHARGE
AI-031
SNVT_count_f
(51)
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
nvoPRS_1_SUCTION
PRESSURES 1
SUCTION
AI-032
SNVT_count_f
(51)
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
nvoPRS_2_DISCH
PRESSURES 2
DISCHARGE
AI-033
SNVT_count_f
(51)
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
nvoPRS_2_SUCTION
PRESSURES 2
SUCTION
AI-034
SNVT_count_f
(51)
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
nvoPRS_3_DISCH
PRESSURES 3
DISCHARGE
AI-035
SNVT_count_f
(51)
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
nvoPRS_3_SUCTION
PRESSURES 3
SUCTION
AI-036
SNVT_count_f
(51)
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
nviRAT_COOL_SP
RAT COOLING
SETP
AV-023
SNVT_count_f
(51)
ON A VAV OR FLEXSYS UNIT THIS VALUE IS USED TO DETER
-
MINE WHEN THE UNIT SHOULD SWITCH TO THE COOLING
MODE (F)
nvoRET_AIR_BY_S
ACTIVE BYPASS
ACTIVE SP
AI-037
SNVT_switch
(95)
A DERIVED VALUE FOR THE CURRENT SET POINT OF THE
RETURN AIR BYPASS DAMPER ON A FLEXSYS UNIT (%)
nvoRET_AIR_ENTH
RETURN AIR
ENTHALPY
AI-038
SNVT_count_f
(51)
ACTUAL RETURN AIR ENTHALPY (BTU/LB)
nvoRET_AIR_HUMD
RETURN AIR
HUMIDITY
AI-039
SNVT_switch
(95)
ACTUAL RETURN AIR RELATIVE HUMIDITY (%)
nvoRET_AIR_TEMP
RETURN AIR TEMP
AI-040
SNVT_count_f
(51)
ACTUAL RETURN AIR TEMPERATURE (F)
RET_FAN_OUT
EXHAUST/RETURN
FAN VFD
AI41
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
nvoRET_FAN_PRES
RETURN FAN
PRESSURE
AI-042
SNVT_count_f
(51)
THE ACTUAL PRESSURE THAT IS USED TO CONTROL THE
RETURN FAN ((IWC)
nvoRET_FAN_STAT
RETURN FAN
STATUS
BI-052
SNVT_switch
(95)
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
nviSAT_HIGH_LIM
SAT HIGH LIMIT
AV-026
SNVT_count_f
(51)
THE UPPER LIMIT FOR THE SUPPLY AIR TEMPEATURE SET
POINT ON A VAV UNIT (F)
nviSAT_LOW_LIM
SAT LOW LIMIT
AV-027
SNVT_count_f
(51)
THE LOWER LIMIT FOR THE SUPPLY AIR TEMPEATURE SET
POINT ON A VAV UNIT (F)
nviSAT_RST_BAS
SUPPLY AIR TEMP
RST BAS
AV-028
SNVT_count_f
(51)
THIS IS AN ANALOG INPUT FROM THE BAS SYSTEM THAT AL
-
LOWS THE RESET OF THE ACTIVE SUPPLY AIR TEMPERATURE
SET POINT ON VAV UNITS. 0 VOLTS USES SAT HIGH LIMIT AND
5 VOLTS USES SAT LOW LIMIT (V). "SAT RST BAS" MUST BE
ENABLED USING THE SERVICE KEY IN ORDER TO USE THIS
FEATURE
nvoSAT_SUC_TMP1
SATURATED
SUCTION TEMP
(TEMPERATURES 1
SUCTION)
AI-043
SNVT_count_f
(51)
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
nvoSAT_SUC_TMP2
SATURATED
SUCTION TEMP
(TEMPERATURES 2
SUCTION)
AI-044
SNVT_count_f
(51)
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
nvoSAT_SUC_TMP3
SATURATED
SUCTION TEMP
(TEMPERATURES 3
SUCTION)
AI-045
SNVT_count_f
(51)
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...