166
JOHNSON CONTROLS
5276178-JIM-C-0118
User Interface Control Center
TABLE 82 - COMPRESSOR SYSTEMS (1, 2, OR 3)
DISPLAY TEXT
PASS
WORD
LEVEL
RANGE
DEFAULT SETTING
LOCATION
SHOW WHEN UNIT TYPE IS
COMP SYS* STATUS
NORMAL - COMP A ON /
NORMAL - COMP B ON /
NORMAL - BOTH ON / NORMAL
- BOTH OFF / SAFETY TRIP
/ SAFETY FAULT / SAFETY
LOCKOUT / LOW AMB INHIBIT /
LOW SUCT TEMP UNL / HIGH DP
UNLOAD / USER DISABLED
DERIVED
ALWAYS
COMP SYS* STATE
1
STOP / RUN / LOCKOUT / AUTO
RESET
DERIVED
OPTIONS /
COMP SYS ALWAYS
CONDENSER FAN
1A (1)
OFF / ON
DERIVED
UNIT CONTROLLER DOES NOT CONTROL
CONDENSER FANS
CONDENSER FAN
1B (2)
OFF / ON
DERIVED
CONDENSER FAN
2A (3)
OFF / ON
DERIVED
CONDENSER FAN
2B (4)
OFF / ON
DERIVED
SAFETY INPUT
LPCO
OKAY - FAULTED
DERIVED
ALWAYS
CHAIN
OKAY - FAULTED
DERIVED
SUCTION TEMP
-20.0º F TO 180.0º F
LOOK UP
TABLE
THIS FEATURE IS NOT AVAILABLE
ON THIS UNIT.
PRESSURE
DISCHARGE *
0 TO 320 PSIG (R410A)
LOOK UP
TABLE
THIS FEATURE IS NOT AVAILABLE
ON THIS UNIT.
SUCTION *
0 TO 800 (R410A)
LOOK UP
TABLE
TEMPERATURE
SUCTION
1
-20.0º F TO 180.0º F
LOOK UP
TABLE
THIS FEATURE IS NOT AVAILABLE
ON THIS UNIT.
SUPERHEAT
0.0º F TO 50.0º F
DERIVED
CURRENT RUN TIME
COMP A
HH:MM:SS
DERIVED
ALWAYS
COMP B
HH:MM:SS
DERIVED
PUMPDOWN
2
USER ENABLED
USER DISABLED
DISABLED
PROGRAM/
COMP SYS.
THIS FEATURE IS NOT AVAILABLE
ON THIS UNIT.
READY TO RUN
COMP A
YES - NO
DERIVED
ALWAYS
COMP B
YES - NO
DERIVED
READY TO STOP
COMP A
YES - NO
DERIVED
ALWAYS
COMP B
YES - NO
DERIVED
SYSTEM
UNLOADING
PRESSURE
2
250 - 450 PSIG
400 PSIG
SETPOINTS/
COMP SYS
THIS FEATURE IS NOT AVAILABLE
ON THIS UNIT.
PRESS TRANS PKG
2
NONE / SYS 1
NONE
OPTIONAL/
COMP SYS ALWAYS
LOW AMBIENT PKG
2
NONE / SYS 1
NONE
OPTIONAL/
COMP SYS ALWAYS
* MAY BE 1, OR 2
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...