TABLE 50 - R410-A PRESSURE / TEMPERATURE CHART
PSIG
TEMP
˚
F
PSIG
TEMP
˚
F
0
-60
78
20
2
-58
80
21
4
-54
85
24
6
-50
90
26
8
-46
95
29
10
-42
100
32
12
-39
105
34
14
-36
110
36
16
-33
115
39
18
-30
120
41
20
-28
125
43
22
-26
130
45
24
-24
135
47
26
-20
140
49
28
-18
145
51
30
-16
150
53
32
-14
160
57
34
-12
170
60
36
-10
180
64
38
-8
190
67
40
-6
200
70
42
-4
210
73
44
-3
220
76
46
-2
225
78
48
0
235
80
50
1
245
83
52
3
255
85
54
4
265
88
56
6
275
90
58
7
285
92
60
8
295
95
62
10
305
97
64
11
325
101
66
13
355
108
68
14
375
112
70
15
405
118
72
16
500
134
74
17
600
149
76
19
700
159
Leak Checking
Leak check compressors, fittings, and piping to assure
no leaks. Verify the evaporator distributor tubes do not
have bare copper touching each other or are against a
sheet metal edge.
If the unit is functioning satisfactorily
during the initial operating period, no
safety trips and the unit controls are
functioning properly, the unit is ready
to be placed into operation.
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...