171
JOHNSON CONTROLS
5276178-JIM-C-0118
6
TABLE 85 - ECONOMIZER
DISPLAY TEXT
PASS
WORD
LEVEL
RANGE
DEFAULT
SETTING LOCATION
SHOW WHEN UNIT TYPE
IS
ECONO SYS
STATUS
NORMAL - ACTIVE /
NORMAL - INACTIVE
/ FAULTED / USER
DISABLED / NONE
DERIVED
ALWAYS
ECONO
INSTALLED
2
NONE / DRYBULB /
SINGLE ENTHALPY /
DUAL ENTHALPY
NONE
OPTIONS / ECONOMIZER
ALWAYS
ECONO
METHOD TO
USE
1
DRY BULB / SINGLE
ENTHALPY / DUAL
ENTHALPY / BEST
AVAILABLE
BEST AVAILABLE
OPTIONS / ECONOMIZER
ECONOMIZER INSTALLED
DOES NOT EQUAL NONE
ECONO
METHOD
ACTIVE
DRY BULB / SINGLE
ENTHALPY / DUAL
ENTHALPY
DERIVED
ECONOMIZER INSTALLED
DOES NOT EQUAL NONE
ECONOMIZER
CONTROL
OUTPUT
0 TO 100%
DERIVED
ECONOMIZER INSTALLED
DOES NOT EQUAL NONE
OUTSIDE AIR
TEMP
-20.0º F TO 180.0º F
LOOK UP TABLE
ECONOMIZER INSTALLED
DOES NOT EQUAL NONE
OUTSIDE AIR
HUMIDITY
0 TO 100%
LOOK UP TABLE
ECONOMIZER INSTALLED
EQUALS SINGLE ENTHALPY
OR DUAL ENTHALPY
ENTHALPY
7.2 TO 204.9 BTU/LB
LOOK UP TABLE
ECONOMIZER INSTALLED
EQUALS SINGLE ENTHALPY
OR DUAL ENTHALPY
RETURN AIR
TEMP
-20.0º F TO 180.0º F
LOOK UP TABLE
ECONOMIZER INSTALLED
EQUALS DUAL ENTHALPY
RETURN AIR
HUMIDITY
0 TO 100%
LOOK UP TABLE
ECONOMIZER INSTALLED
EQUALS DUAL ENTHALPY
ENTHALPHY
7.2 TO 204.9 BTU/LB
LOOK UP TABLE
ECONOMIZER INSTALLED
EQUALS DUAL ENTHALPY
OUTSIDE AIR
ENTHALPY
SETPOINT
1
22.0 TO 40.0 BTU/LB
28.0 BTU/LB
SETPOINTS / ECONOMIZER
ECONOMIZER INSTALLED
DOES NOT EQUAL NONE
ECONOMIZER
SYSTEM
1
USER ENABLED USER
DISABLED
DISABLED
PROGRAM / ECONOMIZER
ECONOMIZER INSTALLED
DOES NOT EQUAL NONE
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...