219
JOHNSON CONTROLS
5276178-JIM-C-0118
7
TABLE 93
-
PARAMETER DEFINITIONS (CONT'D)
MENU ITEM
DEFINITION
COMP SYS 2 STATUS
This is the current operating mode of compressors 3 and 4. The display will show
Normal - Comp A On, Normal - Comp B On, Normal - Both ON, Normal - Both Off,
Safety Trip, Safety Fault, Safety Lockout, Low Amb Inhibit, Low Suct Temp Unl, High
DP Unload, or User Disabled.
COMP SYS 3 STATUS
This is the current operating mode of the system 3 compressors. The display will
show Normal - Comp A On, Normal - Comp B On, Normal - Both ON, Normal - Both
Off, Safety Trip, Safety Fault, Safety Lockout, Low Amb Inhibit, Low Suct Temp Unl,
High DP Unload, or User Disabled.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
CONDENSER FAN 1A/1
Condenser Fan Operation is not controlled by the Unit Controller.
CONDENSER FAN 1B/2
Condenser Fan Operation is not controlled by the Unit Controller.
CONDENSER FAN 2A/3
Condenser Fan Operation is not controlled by the Unit Controller.
CONDENSER FAN 2B/4
Condenser Fan Operation is not controlled by the Unit Controller.
CONDENSER FAN 3A/5
This identifies if the Unit Controller has sent a Binary output to Condenser Fan 3A
/5.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
CONDENSER FAN 3B/6
This identifies if the Unit Controller has sent a Binary output to Condenser Fan 3B/6.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
.
CONTINUOUS VENT
This parameter is programmed through the PROGRAM key. This is only used on a
Constant Volume unit. When this parameter is enabled the supply blower will operate
whenever the unit is in the Occupied mode. The choices are USER ENABLED or
USER DISABLED.
CONTROL METHOD
This parameter is programmed through the OPTIONS key and identifies the control
method being used on a Constant Volume unit. The choices are Staged, Wired Zone
Temp or Comm Zone Temp.
COOLING CONTROL OFFSET
This is the control band the unit is trying to maintain. The control band is the Active
Set Point plus or minus the Cooling Control Offset. If the temperature is above this
band additional cooling is required, if the temperature is below this band cooling is
decreased.
CURRENT OPER MODE
This is the current operating mode of the unit. The display will show Occ Standby, Occ
Cooling Low, Occ Cooling High, Occ Heating Low, Occ Heating High, Unocc Standby,
Unocc Cooling Low, Unocc Cooling High, Unocc Heating Low, Unocc Heating High,
Morning Warm-up, Comfort Vent Cooling, Comfort Vent Heating, Occupied Cooling,
Occupied Heating, Unoccupied Cooling, Unoccupied Heating, Occ Cooling W/O
Bypass, Occ Cooling W Bypass, or Underfloor Temp Override.
CURRENT RUN TIME COMP A
This is the amount of time the compressor has been in operation during the current
cycle. This is shown for each compressor of every compressor system. (Compressor
1 and 3).
CURRENT RUN TIME COMP B
This is the amount of time the compressor has been in operation during the current
cycle. This is shown for each compressor of every compressor system. (Compressor
2 and 4).
DAILY WARM UP TIME
This is the time it takes to bring the Return Air Temperature up to set point during
Adaptive Morning Warm Up. The Unit Controller uses this value in the calculation of
Daily Warm Up Time Day 1.
DAILY WARM UP TIME DAY 1
This is the Morning Warm Up time the Unit Controller recorded during the previous
day 1. This value is used to calculate the current Morning Warm initiate time for
Adaptive Morning Warm Up.
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...