199
JOHNSON CONTROLS
5276178-JIM-C-0118
6
TABLE 90
-
BACNET MS/TP, MODBUS, BACNET IP (CONT'D)
(See notes at end of table)
BACnet NAME
USER
INTERFACE
NAME
READ/
WRITE
BACnet
OBJECT
TYPE AND
INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
OCC_STATE
OCCUPANCY
STATE
R
BI36
1317
IDENTIFIES THE STATUS OF THE HARDWIRED
BINARY INPUT (ENA - ENABLED - OCCUPIED; DIS -
DISABLED UNOCCUPIED)
OCC_ZN_COOL
OCCUPIED ZONE
COOLING SETP
R/W
AV21
1046
THE OCCUPIED ZONE COOLING SET POINT (F)
OCC_ZN_HEAT
OCCUPIED ZONE
HEATING SETP
R/W
AV22
1047
THE OCCUPIED ZONE HEATING SET POINT (F)
OCCUPNCY_CMD
OCCUPANCY
COMMAND
R/W
AV88
1113
THIS BAS COMMAND ALLOWS THE UNIT TO BE
PLACED IN THE OCCUPIED OR UNOCCUPIED
MODE (0 = UNOCCUPIED / 1 = OCCUPIED)
PRS_1_DISCH
PRESSURES 1
DISCHARGE
R
AI31
544
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
PRS_1_SUCTION
PRESSURES 1
SUCTION
R
AI32
545
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
PRS_2_DISCH
PRESSURES 2
DISCHARGE
R
AI33
546
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
PRS_2_SUCTION
PRESSURES 2
SUCTION
R
AI34
547
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
PRS_3_DISCH
PRESSURES 3
DISCHARGE
R
AI35
548
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
PRS_3_SUCTION
PRESSURES 3
SUCTION
R
AI36
549
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
PUMP_DOWN
PUMP DOWN
ENABLE
R/W
AV(BV)89
1114
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
PUMP_DOWN 1
PUMP DOWN
LLSV 1
R
BI37
1318
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
PUMP_DOWN 2
PUMP DOWN
LLSV 2
R
BI38
1319
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
PUMP_DOWN 3
PUMP DOWN
LLSV 3
R
BI39
1320
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
RAT_COOL_SP
RAT COOLING
SETP
R/W
AV23
1048
ON A VAV OR FLEXSYS UNIT THIS VALUE IS USED
TO DETERMINE WHEN THE UNIT SHOULD SWITCH
TO THE COOLING MODE (F)
RAT_HIGH_SAT
RAT FOR HIGH SAT
R/W
AV24
1049
THE RETURN TEMPERATURE THE CONTROL USES
WHEN USING RETURN AIR SAT RESET TO SWITCH
TO THE SAT HIGH LIMIT SET POINT (F)
RAT_LOW_SAT
RAT FOR LOW SAT
R/W
AV25
1050
THE RETURN TEMPERATURE THE CONTROL USES
WHEN USING RETURN AIR SAT RESET TO SWITCH
TO THE SAT LOW LIMIT SET POINT (F)
RDY_RUN_C1A
READY TO RUN
COMP 1A
R
BI40
1321
IDENTIFIES IF COMPRESSOR 1 IS READY TO RUN
IF THE COMPRESSOR IS OFF (YES / NO)
RDY_RUN_C1B
READY TO RUN
COMP 1B
R
BI41
1322
IDENTIFIES IF COMPRESSOR 2 IS READY TO RUN
IF THE COMPRESSOR IS OFF (YES / NO)
RDY_RUN_C2A
READY TO RUN
COMP 2A
R
BI42
1323
IDENTIFIES IF COMPRESSOR 3 IS READY TO RUN
IF THE COMPORESSOR IS OFF (YES / NO)
RDY_RUN_C2B
READY TO RUN
COMP 2B
R
BI43
1324
IDENTIFIES IF COMPRESSOR 4 IS READY TO RUN
IF THE COMPRESSOR IS OFF (YES / NO)
RDY_RUN_C3A
READY TO RUN
COMP 3A
R
BI44
1325
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...